Watlow EZ-ZONE
®
PM Integrated Controller 48 Chapter 5 Operations Page
Operations Page
Display
Parameter name
Description
Range Default
Parameter
Appears in
Menu When
Modbus Rela-
tive Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
No Dis-
play
Alarm (1 to 4)
Alarm Clear Re-
quest
Write to this register
to clear an alarm
Clear (1003)
0
No param-
eter
Instance 1
Map 1 Map 2
1504 1904
Offset to next
instance (Map1
1 equals +50,
Map 2 equals
+60)
0x6D (109)
1 to 4
0xD (13)
- - - - uint
W
No Dis-
play
Alarm (1 to 4)
Alarm Silence Re-
quest
Write to this register
to silence an alarm
Silence (1010)
0
No param-
eter
Instance 1
Map 1 Map 2
1506 1906
Offset to next
instance (Map1
1 equals +50,
Map 2 equals
+60)
0x6D (109)
1 to 4
0xE (14)
- - - - uint
W
No Dis-
play
Alarm (1 to 4)
Alarm Silenced
Write to this register
to silence an alarm
Yes (106)
No (59)
No param-
eter
Instance 1
Map 1 Map 2
1500 1900
Offset to next
instance (Map1
1 equals +50,
Map 2 equals
+60)
0x6D (109)
1 to 4
0x0B (11)
- - - - uint
R
No Dis-
play
Alarm (1 to 4)
Alarm Latched
Write to this register
to silence an alarm
Yes (106)
No (59)
No param-
eter
Instance 1
Map 1 Map 2
1498 1898
Offset to next
instance (Map1
1 equals +50,
Map 2 equals
+60)
0x6D (109)
1 to 4
0x0A (10)
- - - - uint
R
[CUrr]
[oPEr]
Current Menu
[`C;hi]
[ C.hi]
Current (1)
High Set Point
Set the current value
that will trigger a
high heater error
state.
-1,999.000 to
9,999.000
50.0 If 9th
digit in part
number is a
"T" and cur-
rent sides is
set to high
or both.
Instance 1
Map 1 Map 2
1134 1374
0x73 (115)
1
8
- - - - float
RWES
[`C;Lo]
[ C.Lo]
Current (1)
Low Set Point
Set the current value
that will trigger a
low heater error
state.
-1,999.000 to
9,999.000
0.0 If 9th
digit in part
number is a
"T" and cur-
rent sides is
set to low or
both.
Instance 1
Map 1 Map 2
1136 1376
0x73 (115)
1
9
- - - - float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E: EE-
PROM
S: User
Set