Watlow EZ-ZONE
®
PM Integrated Controller 49 Chapter 5 Operations Page
Operations Page
Display
Parameter name
Description
Range Default
Parameter
Appears in
Menu When
Modbus Rela-
tive Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[`CU;r]
[ CU.r]
Current (1)
Read
View the most recent
current value moni-
tored by the current
transformer.
-1,999.000 to
9,999.000
If 9th
digit in part
number is a
"T".
Instance 1
Map 1 Map 2
1120 1360
0x73 (115)
1
1
- - - - float
R
[`C;Er]
[ C.Er]
Current (1)
Error
View the cause of
the most recent load
fault.
[nonE] None (61)
[Shrt] Shorted (127)
[open] Open (65)
None If 9th
digit in part
number is a
"T".
Instance 1
Map 1 Map 2
1160 1400
0x73 (115)
1
2
- - - - uint
R
[`h;Er]
[ h.Er]
Current (1)
Heater Error
View the cause of
the most recent load
fault monitored by
the current trans-
former.
[nonE] None (61)
[high] High (37)
[Low] Low (53)
None If 9th
digit in part
number is a
"T".
Instance 1
Map 1 Map 2
1124 1364
0x73 (115)
1
3
- - - - uint
R
No Dis-
play
Current (1)
Error Status
View the cause of
the most recent load
fault
[none] None (61)
[fail] Fail (32)
- - - - If 9th
digit in part
number is a
"T".
Instance 1
Map 1 Map 2
1160 1400
0x73 (115)
1
21
- - - - uint
R
[MAt]*
[oPEr]
Math Menu
[`Su;A]
[ Sv.A]
Math (1)
Source Value A
View the value of
Source A or Linear-
ization 1.
-1,999.000 to
9,999.000°Forunits
-1,128.000 to
5,537.000°C
0.0 Always if
digit 12 of
part num-
ber is "C".
Instance 1
Map 1 Map 2
- - - - 3030
0x7D (125)
1
0x10 (16)
- - - - float
RWES
[`Su;b]
[ Sv.b]
Math (1)
Source Value B
View the value of
Source B or Linear-
ization 2.
-1,999.000 to
9,999.000°Forunits
-1,128.000 to
5,537.000°C
0.0 Math Func-
tion (Setup
Page) is set
to Process
Scale, Devi-
ation Scale.
Instance 1
Map 1 Map 2
- - - - 3032
0x7D (125)
1
0x11 (17)
- - - - float
RWES
[`Su;E]
[ Su.E]
Math (1)
Source Value E
Disables Process/
Deviation scale when
on.
[`off] Off (62)
[``on] On (63)
0 Math Func-
tion (Setup
Page) is set
to Process
Scale, Devi-
ation Scale.
Instance 1
Map 1 Map 2
- - - - 3038
0x7D (125)
1
0x14 (20)
- - - - uint
RWES
[oFSt]
[oFSt]
Math (1)
Offset
Set an offset to be
applied to this func-
tion's output.
-1,999.000 to
9,999.000°Forunits
-1,128.000 to
5,537.000°C
0.0 Math Func-
tion (Setup
Page) is set
to Process
Scale, Devi-
ation Scale.
Instance 1
Map 1 Map 2
- - - - 3044
0x7D (125)
1
0x17 (23)
- - - - float
RWES
[``o;u]
[ o.v]
Math (1)
Output Value
View the value of this
function's output.
-1,999.000 to
9,999.000°Forunits
-1,128.000 to
5,537.000°C
0.0 Math Func-
tion (Setup
Page) is set
to Process
Scale, Devi-
ation Scale.
Instance 1
Map 1 Map 2
- - - - 3042
0x7D (125)
1
0x16 (22)
- - - - float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E: EE-
PROM
S: User
Set