PM Integrated Controller • 60 • Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[`iP;1]
[ ip.1]
Linearization (1 to 2)
Input Point 1
Set the value that
will be mapped to
output 1.
-1,999.000 to 9,999.000 0.0 Always Instance 1
Map 1 Map 2
- - - - 3574
Instance 2
Map 1 Map 2
- - - - 3644
0x86 (134)
1 to 2
8
157 float
RWES
[`oP;1]
[ op.1]
Linearization (1 to 2)
Output Point 1
Set the value that
will be mapped to
input 1.
-1,999.000 to 9,999.000 0.0 Always Instance 1
Map 1 Map 2
- - - - 3594
Instance 2
Map 1 Map 2
- - - - 3664
0x86 (134)
1 to 2
0x12 (18)
158 float
RWES
[`iP;2]
[ ip.2]
Linearization (1 to 2)
Input Point 2
Set the value that
will be mapped to
output 2.
-1,999.000 to 9,999.000 1.0 Always Instance 1
Map 1 Map 2
- - - - 3576
Instance 2
Map 1 Map 2
- - - - 3646
0x86 (134)
1 to 2
9
159 float
RWES
[`oP;2]
[ op.2]
Linearization (1 to 2)
Output Point 2
Set the value that
will be mapped to
input 2.
-1,999.000 to 9,999.000 1.0 Always Instance 1
Map 1 Map 2
- - - - 3597
Instance 2
Map 1 Map 2
- - - - 3667
0x86 (134)
1 to 2
0x13 (19)
160 float
RWES
[`iP;3]
[ ip.3]
Linearization (1 to 2)
Input Point 3
Set the value that
will be mapped to
output 3.
-1,999.000 to 9,999.000 2.0 Always Instance 1
Map 1 Map 2
- - - - 3578
Instance 2
Map 1 Map 2
- - - - 3648
0x86 (134)
1 to 2
0xA (10)
161 float
RWES
[`oP;3]
[ op.3]
Linearization (1 to 2)
Output Point 3
Set the value that
will be mapped to
input 3.
-1,999.000 to 9,999.000 2.0 Always Instance 1
Map 1 Map 2
- - - - 3598
Instance 2
Map 1 Map 2
- - - - 3668
0x86 (134)
1 to 2
0x14 (20)
162 float
RWES
[`iP;4]
[ ip.4]
Linearization (1 to 2)
Input Point 4
Set the value that
will be mapped to
output 4.
-1,999.000 to 9,999.000 3.0 Always Instance 1
Map 1 Map 2
- - - - 3581
Instance 2
Map 1 Map 2
- - - - 3651
0x86 (134)
1 to 2
0xB (11)
163 float
RWES
[`oP;4]
[ op.4]
Linearization (1 to 2)
Output Point 4
Set the value that
will be mapped to
input 4.
-1,999.000 to 9,999.000 3.0 Always Instance 1
Map 1 Map 2
- - - - 3600
Instance 2
Map 1 Map 2
- - - - 3670
0x86 (134)
1 to 2
0x15 (21)
164 float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other
interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set