PM Integrated Controller • 62 • Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[`iP;9]
[ ip.9]
Linearization (1 to 2)
Input Point 9
Set the value that
will be mapped to
output 9.
-1,999.000 to 9,999.000 8.0 Always Instance 1
Map 1 Map 2
- - - - 3590
Instance 2
Map 1 Map 2
- - - - 3660
0x86 (134)
1 to 2
0x10 (16)
173 float
RWES
[`oP;9]
[ op.9]
Linearization (1 to 2)
Output Point 9
Set the value that
will be mapped to
input 9.
-1,999.000 to 9,999.000 8.0 Always Instance 1
Map 1 Map 2
- - - - 3610
Instance 2
Map 1 Map 2
- - - - 3680
0x86 (134)
1 to 2
0x1A (26)
174 float
RWES
[iP;10]
[ip.10]
Linearization (1 to 2)
Input Point 10
Set the value that
will be mapped to
output 10.
-1,999.000 to 9,999.000 9.0 Always Instance 1
Map 1 Map 2
- - - - 3592
Instance 2
Map 1 Map 2
- - - - 3662
0x86 (134)
1 to 2
0x11 (17)
175 float
RWES
[oP;10]
[op.10]
Linearization (1 to 2)
Output Point 10
Set the value that
will be mapped to
input 10.
-1,999.000 to 9,999.000 9.0 Always Instance 1
Map 1 Map 2
- - - - 3612
Instance 2
Map 1 Map 2
- - - - 3682
0x86 (134)
1 to 2
0x1B (27)
176 float
RWES
[``Pu]*
[`Set]
Process Value
[``Fn]
[ Fn]
Process Value (1 to 2)
Function
Set the function that
will be applied to the
source or sources.
Note:
Differential and
Ratio not available
using instance 2.
[`oFF] Off (62)
[usla] Vaisala RH Compen-
sation (1648)
[`W;b] Wet Bulb/Dry Bulb
(1369)
[`S;bA] Sensor Backup (1201)
[rAti] Ratio (1374)
[diFF] Differential (1373)
[root] Square Root (1380)
[`alt] **Pressure to Alti-
tude (1649)
Off Always if
part num-
ber digit 4
is C, R, J, B,
E or N.
PM4, 8 and
9 only
Instance 1
Map 1 Map 2
- - - - 3320
Instance 2
Map 1 Map 2
- - - - 3390
0x7E (126)
1 to 2
0x15 (21)
123 uint
RWES
[p;unt]
[P.unt]
Process Value (1 to 2)
Pressure Units
Set the units that
will be applied to the
source.
[`psi] Pounds per Square
Inch (1671)
[pasc] Pascal (1674)
[atm] Atmosphere (1675)
[mbr] Millibar (1672)
[torr] Torr (1673)
PSI Always Instance 1
Map 1 Map 2
- - - - 3334
Instance 2
Map 1 Map 2
- - - - 3404
0x7E (126)
1 to 2
0x1C (28)
- - - - uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other
interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set
** Pressure Altitude calculation is based on the International Standard Atmosphere 1976