PM Integrated Controller • 63 • Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[a;unt]
[A.unt]
Process Value (1 to 2)
Altitude Units
Set the units that
will be applied to the
source.
[`Hft] Kilofeet (1677)
[``ft] Feet (1676)
HFt Always Instance 1
Map 1 Map 2
- - - - 3336
Instance 2
Map 1 Map 2
- - - - 3406
0x7E (126)
1 to 2
0x1D (29)
- - - - uint
RWES
[`b;pr]
[ b.Pr]
Process Value (1 to 2)
Barometric Pres-
sure
Set the units that
will be applied to the
source.
10.0 to 16.0 14.7 Always Instance 1
Map 1 Map 2
- - - - 3338
Instance 2
Map 1 Map 2
- - - - 3408
0x7E (126)
1 to 2
0x1E (30)
- - - - float
RWES
[`Fil]
[ FiL]
Process Value (1 to 2)
Filter
Filtering smooths out
the output signal of
this function block.
Increase the time to
increase filtering.
0.0 to 60.0 seconds 0.0 Always Instance 1
Map 1 Map 2
- - - - 3330
Instance 2
Map 1 Map 2
- - - - 3400
0x7E (126)
1 to 2
0x1A (26)
- - - - float
RWES
[`dio]
[`Set]
Digital Input/
Output Menu
[`dir]
[ dir]
Digital Input/Output
(5 to 12)
Direction
Set this function to
operate as an input
or output.
[OtPt] Output (68)
[iCon] Input Dry Contact
(44)
[``in] Input Voltage (193)
Output Always Instance 1
Map 1 Map 2
1000 1120
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
5 to 12
1
82 uint
RWES
[``Fn]
[ Fn]
Digital Output (5 to
12)
Function
Select what func-
tion will drive this
output.
[`oFF] Off (62)
[lim] Limit (126)
[Ent;b] Profile Event Out B
(234)
[Ent;A] Profile Event Out A
(233)
[SoF;2] Special Function Out-
put 2 (1533)
[SoF;1] Special Function Out-
put 1 (1532)
[CooL] Cool Power, Control
Loop (161)
[heat] Heat Power, Control
Loop (160)
[ALM] Alarm (6)
Off Direction is
set to Out-
put.
Instance 1
Map 1 Map 2
1008 1128
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
5 to 12
5
83 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other
interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set