PM Integrated Controller 64 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[``Fi]
[ Fi]
Digital Output (5 to
12)
Function Instance
Set the instance of
the function selected
above.
1 to 4 1 Direction is
set to Out-
put.
Instance 1
Map 1 Map 2
1010 1130
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
5 to 12
6
84 uint
RWES
[`o;Ct]
[ o.Ct]
Digital Output (5 to
12)
Control
Set the output con-
trol type. This pa-
rameter is only used
with PID control, but
can be set anytime.
[`Ftb] Fixed Time Base (34)
[`utb] Variable Time Base
(103)
Fixed
Time
Base
Direction is
set to Out-
put.
Instance 1
Map 1 Map 2
1002 1122
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
5 to 12
2
85 uint
RWES
[`o;tb]
[ o.tb]
Digital Output (5 to
12)
Time Base
Set the time base
for fixed-time-base
control.
[ 0.1 for Fast and Bi-Direc-
tional outputs, 5.0 for Slow
outputs] to 60
5.0 Control
is set to
Fixed
Time
Base.
Instance 1
Map 1 Map 2
1004 1124
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
5 to 12
3
86 float
RWES
[`o;Lo]
[ o.Lo]
Digital Output (5 to
12)
Low Power Scale
The power output
will never be less
than the value speci-
fied and will rep-
resent the value at
which output scaling
begins.
0.0 to 100.0 0.0 Direction is
set to Out-
put and
Source
is set to
Heat or
Cool.
Instance 1
Map 1 Map 2
1016 1136
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
5 to 12
9
87 float
RWES
[`o;hi]
[ o.hi]
Digital Output (5 to
12)
High Power Scale
The power output
will never be greater
than the value speci-
fied and will rep-
resent the value at
which output scaling
stops.
0.0 to 100.0 100.0 Direction is
set to Out-
put and
Source
is set to
Heat or
Cool.
Instance 1
Map 1 Map 2
1018 1138
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
5 to 12
0xA (10)
88 float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other
interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set