Watlow EZ-ZONE
®
PM Integrated Controller • 66 • Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[``Fi]
[ Fi]
Digital Input (5 to 12)
Function Instance
Select which Digital
Input will be trig-
gered by a true state.
0 to 4 0 Direction is
set to Out-
put.
Instance 1
Map 1 Map 2
1326 -
Offset to next
instance (Map
1 & Map 2)
equals +20
0x6E (110)
5 to 12
4
139 uint
RWES
[Lim]
[`Set]
Limit Menu
[`L;Sd]
[ L.Sd]
Limit (1)
Sides
Select which side or
sides of the process
value will be moni-
tored.
[both] Both (13)
[high] High (37)
[LoW] Low (53)
Both Always Instance 1
Map 1 Map 2
688 728
0x70 (112)
1
5
40 uint
RWES
[`L;hy]
[ L.hy]
Limit (1)
Hysteresis
Set the hysteresis
for the limit func-
tion. This determines
how far into the safe
range the process
value must move be-
fore the limit can be
cleared.
0.001to9,999.000°Forunits
0.001to5,555.000°C
3.0°For
units
2.0°C
Always Instance 1
Map 1 Map 2
682 722
0x70 (112)
1
2
41 float
RWES
[SP;Lh]
[SP.Lh]
Limit (1)
Set Point Limit
High
Set the high end of
the limit set point
range.
-1,999.000 to 9,999.000 9,999.000 Always Instance 1
Map 1 Map 2
696 736
0x70 (112)
1
9
42 float
RWES
[SP;Ll]
[SP.LL]
Limit (1)
Set Point Limit
Low
Set the low end of
the limit set point
range.
-1,999.000 to 9,999.000 -1,999.000 Always Instance 1
Map 1 Map 2
698 738
0x70 (112)
1
0x0A (10)
43 float
RWES
[`L;it]
[ L.it]
Limit
Integrate
In a limit state the
controller will turn
off the outputs, ter-
minate an active pro-
file and freeze PID
and TRU-TUNE+
®
calculations.
[``no] No (59)
[`YES] Yes (106)
No Always Instance 1
Map 1 Map 2
694 734
0x70 (112)
1
8
- - - - uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other
interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set