Watlow EZ-ZONE
®
PM Integrated Controller 70 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[SP;Lo]
[SP.Lo]
Control Loop (1 to 2)
Set Point Open
Limit Low
Set the minimum value
of the open-loop set
point range.
-100 to 100% -100 Always Instance 1
Map 1 Map 2
2168 2649
Instance 2
Map 1 Map 2
2248 2728
0x6B (107)
1 to 2
5
54 float
RWES
[SP;hi]
[SP.hi]
Control Loop (1 to 4)
Set Point Open
Limit High
Set the maximum
value of the open-
loop set point range.
-100 to 100% 100 Always Instance 1
Map 1 Map 2
2170 2650
Instance 2
Map 1 Map 2
2250 2730
0x6B (107)
1 to 2
6
55 float
RWES
[otpt]
[`Set]
Output Menu
[``Fn]
[ Fn]
Output Digital (1 to 4)
Function
Select what func-
tion will drive this
output.
[`oFF] Off (62)
[LiM] Limit (126)
[Ent;b] Profile Event Out B
(234)
[Ent;A] Profile Event Out A
(233)
[SoF;2] Special Function Out-
put 1 (1533)
[SoF;1] Special Function Out-
put 1 (1532)
[Cool] Cool (20)
[heat] Heat (36)
[ALM] Alarm (6)
Output 1 -
Heat
Output 2 -
Alarm
Output 3 -
Off
Output 4 -
Off
Instance 1
Map 1 Map 2
888 1008
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
1 to 4
5
83 uint
RWES
[``Fi]
[ Fi]
Output (1 to 4)
Function Instance
Set the instance of
the function selected
above.
1 to 4 1 Instance 1
Map 1 Map 2
890 1010
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
1 to 4
6
84 uint
RWES
[`o;Ct]
[ o.Ct]
Output (1 to 4)
Control
Set the output con-
trol type. This pa-
rameter is only used
with PID control, but
can be set anytime.
[`Ftb] Fixed Time Base (34)
[`utb] Variable Time Base
(103)
Fixed
Time
Base
Instance 1
Map 1 Map 2
882 1002
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
1 to 4
2
85 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other
interfaces.
* Available with PM4, PM8 and PM9 models only