Watlow EZ-ZONE
®
PM Integrated Controller • 71 • Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[`o;tb]
[ o.tb]
Output (1 to 4)
Time Base
Set the time base
for fixed-time-base
control.
0.1 to 60.0 seconds (solid-
state relay or switched dc)
5.0 to 60.0 seconds (mechani-
cal relay or no-arc power
control)
0.1 sec.
[SSR &
sw dc]
20.0 sec.
[mech,
relay,
no-arc]
Control
is set to
Fixed
Time
Base.
Instance 1
Map 1 Map 2
884 1004
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
1 to 4
3
86 float
RWES
[`o;Lo]
[ o.Lo]
Output (1 to 4)
Low Power Scale
The power output
will never be less
than the value speci-
fied and will rep-
resent the value at
which output scaling
begins.
0.0 to 100.0% 0.0% Source is
set to PID
Heat or
Cool.
Instance 1
Map 1 Map 2
896 1016
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
1 to 4
9
87 float
RWES
[`o;hi]
[ o.hi]
Output (1 to 4)
High Power Scale
The power output
will never be greater
than the value speci-
fied and will rep-
resent the value at
which output scaling
stops.
0.0 to 100.0% 100.0% Source is
set to PID
Heat or
Cool.
Instance 1
Map 1 Map 2
898 1018
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
1 to 4
0xA (10)
88 float
RWES
[`o;ty]
[ o.ty]
Output (1 or 3 pro-
cess)
Type
Select whether the
process output will
operate in volts or
milliamps.
[uoLt] Volts (104)
[`MA] Milliamps (112)
Volts Always if
digit 6 or 10
of the part
number is
an "F".
Instance 1
Map 1 Map 2
720 840
Instance 3
Map 1 Map 2
800 920
0x76 (118)
1 or 3
1
95 uint
RWES
[``Fn]
[ Fn]
Output Process (1
or 3)
Function
Set the type of func-
tion that will drive
this output.
[`oFF] Off (62)
[dupl] Duplex (212)
[Cool] Cool (20)
[heat] Heat (36)
[rmt] Retransmit (213)
[Ent;b] Profile Event Out B
(234)
[Ent;A] Profile Event Out A
(233)
[ALM] Alarm (6)
Off Always if
digit 6 or
10 of part
number is
an "F".
Instance 1
Map 1 Map 2
722 842
Instance 3
Map 1 Map 2
802 922
0x76 (118)
1 or 3
2
96 uint
RWES
[`r;Sr]
[ r.Sr]
Output (1 or 3 pro-
cess)
Retransmit Source
Select the value that
will be retransmit-
ted.
[``Ai] Analog Input (142)
[StPt] Set Point (85)
[CUrr] Current (22)
Analog
Input
Always if
digit 6 or
10 of part
number is
an "F".
Instance 1
Map 1 Map 2
724 844
Instance 3
Map 1 Map 2
804 924
0x76 (118)
1 or 3
3
97 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other
interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set