Watlow EZ-ZONE
®
PM Integrated Controller • 77 • Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[`sof]*
[`set]
Special Output Function Menu
[``Fn]
[ Fn]
Special Output (1)
Function
Set the function to
match the device it
will operate.
[`oFF] Off (62)
[`uA;C] Motorized Valve
(1508)
[`Co;C] Compressor Control
(1506)
Off Always if
12th digit of
part num-
ber is a "C".
PM4, 8 and
9 only
Instance 1
Map 1 Map 2
- - - - 3856
0x87 (135)
1
9
181 uint
RWES
[SFn;A]
[SFn.A]
Special Output (1)
Source Function A
Set the type of func-
tion that will be used
for this source.
[nonE] None (61)
[PWr] Power, Control Loop
(73)
[`h;Pr] Heat Power, Control
Loop (160)
[`C;Pr] Cool Power, Control
Loop (161)
None Function is
not set to
Off.
Instance 1
Map 1 Map 2
- - - - 3840
0x87 (135)
1
1
182 uint
RWES
[`Si;A]
[ Si.A]
Special Output (1)
Source Instance A
Set the instance of
the function selected
above.
1 to 2 1 Function is
not set to
Off.
Instance 1
Map 1 Map 2
- - - - 3844
0x87 (135)
1
3
183 uint
RWES
[SFn;b]
[SFn.b]
Special Output (1)
Source Function B
Set the type of func-
tion that will be used
for this source.
[nonE] None (61)
[PWr] Power, Control Loop
(73)
[`h;Pr] Heat Power, Control
Loop (160)
[`C;Pr] Cool Power, Control
Loop (161)
None Function
is set to
Compres-
sor.
Instance 1
Map 1 Map 2
- - - - 3842
0x87 (135)
1
2
184 uint
RWES
[`Si;B]
[ Si.b]
Special Output (1)
Source Instance B
Set the instance of
the function selected
above.
1 to 2 1 Function
is set to
Compres-
sor.
Instance 1
Map 1 Map 2
- - - - 3846
0x87 (135)
1
4
185 uint
RWES
[Pon;A]
[Pon.A]
Special Output (1)
Power On Level A
Compressor 1 power
on level.
-100.00 to 100.00% 0 Function
is set to
Compres-
sor.
Instance 1
Map 1 Map 2
- - - - 3874
0x87 (135)
1
0x12 (18)
186 float
RWES
[PoF;A]
[PoF.A]
Special Output (1)
Power Off Level A
Compressor 1 power
off level.
-100.00 to 100.00% 5 Function
is set to
Compres-
sor.
Instance 1
Map 1 Map 2
- - - - 3876
0x87 (135)
1
0x13 (19)
187 float
RWES
[Pon;b]
[Pon.b]
Special Output (1)
Power On Level B
Compressor 2 power
on level.
-100.00 to 100.00% 0 Function
is set to
Compres-
sor.
Instance 1
Map 1 Map 2
- - - - 3878
0x87 (135)
1
0x14 (20)
188 float
RWES
[PoF;b]
[PoF.b]
Special Output (1)
Power Off Level B
Compressor 1 power
off level.
-100.00 to 100.00% 5 Function
is set to
Compres-
sor.
Instance 1
Map 1 Map 2
- - - - 3880
0x87 (135)
1
0x15 (21)
189 float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other
interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set