Watlow EZ-ZONE
®
PM Integrated Controller • 76 • Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[MAt]*
[`Set]
Math Menu
[``Fn]
[ Fn]
Math (1)
Function
Set the operator that
will be applied to the
sources.
[`oFF] Off (62)
[`P;SC] Process Scale (1371)
[`d;SC] Deviation Scale
(1372)
Off Always if
9th digit of
part num-
ber is a "C"
or "J" AND
12th digit is
a "C".
PM8 and 9
only
Instance 1
Map 1 Map 2
- - - - 3040
0x7D (125)
1
0x15 (21)
128 uint
RWES
[SFn;e]
[SFn.E]
Special Output (1)
Source Function E
Set the type of func-
tion that will be used
for this source.
[nonE] None (61)
[`fUn] Function Key (1001)
[`dio] Digital I/O (1142)
None Function is
not set to
Off.
Instance 1
Map 1 Map 2
- - - - 3008
0x7D (125)
1
5
- - - - uint
RWES
[`si;e]
[ Si.E]
Math (1)
Source Instance
Set the instance of
the function selected
above.
1 to 12 1 If function
is not set to
off.
Instance 1
Map 1 Map 2
- - - - 3018
0x7D (125)
1
0xA (10)
float
RWES
[`S;Lo]
[ S.Lo]
Math (1)
Input Scale Low
This value will cor-
respond to Output
Range Low.
-1,999.000 to 9,999.000 0.0 Always Instance 1
Map 1 Map 2
- - - - 3046
0x7D (125)
1
0x18 (24)
129 float
RWES
[`S;hi]
[ S.hi]
Math (1)
Input Scale High
This value will cor-
respond to Output
Range High.
-1,999.000 to 9,999.000 1.0 Always Instance 1
Map 1 Map 2
- - - - 3048
0x7D (125)
1
0x19 (25)
130 float
RWES
[`r;Lo]
[ r.Lo]
Math (1)
Output Range Low
This value will corre-
spond to Input Scale
Low.
-1,999.000 to 9,999.000 0.0 Always Instance 1
Map 1 Map 2
- - - - 3050
0x7D (125)
1
0x1A (26)
131 float
RWES
[`r;hi]
[ r.hi]
Math (1)
Output Range High
This value will corre-
spond to Input Scale
High.
-1,999.000 to 9,999.000 1.0 Always Instance 1
Map 1 Map 2
- - - - 3052
0x7D (125)
1
0x1B (27)
132 float
RWES
[`FiL]
[ FiL]
Math (1)
Filter
Filtering smooths out
the output signal of
this function block.
Increase the time to
increase filtering.
0.0 to 60.0 seconds 0.0 Always Instance 1
Map 1 Map 2
- - - - 3054
0x7D (125)
1
0x1C (28)
- - - - float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other
interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set