Watlow EZ-ZONE
®
PM Integrated Controller • 75 • Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[`A;dL]
[ A.dL]
Alarm (1 to 4)
Delay
Set the span of time
that the alarm will
be delayed after the
process value exceeds
the alarm set point.
0 to 9,999 seconds 0 Type is not
set to Off.
Instance 1
Map 1 Map 2
1520 1920
Offset to next
instance (Map
1 equals +50,
for Map 2
equals +60)
0x6D (109)
1 to 4
0x15 (21)
31 uint
RWES
[CUrr]
[`Set]
Current Menu
[`C;Sd]
[ C.Sd]
Current (1)
Sides
Select which side or
sides will be moni-
tored.
[`oFF] Off (62)
[high] High (37)
[low] Low (53)
[both] Both (13)
off Always if
9th digit
in part
number is
"T".
Instance 1
Map 1 Map 2
1128 1368
0x73 (115)
1
5
145 uint
RWES
[`C;Ur]
[ C.Ur]
Current (1)
Read Enable
Display under/over-
range current.
No (59)
Yes (106)
no Always Instance 1
Map 1 Map 2
1126 1366
0x73 (115)
1
4
146 uint
RWES
[`C;dt]
[ C.dt]
Current (1)
Detection Thresh-
old
For factory adjust-
ment only.
3 to 59 9 Always Instance 1
Map 1 Map 2
1142 1382
0x73 (115)
1
0xC (12)
147 uint
RWES
[`C;SC]
[ C.SC]
Current (1)
Scaling
Adjust scaling to
match the transform-
er's high range.
0 to 9,999.000 50.0 Always Instance 1
Map 1 Map 2
1162 1402
0x73 (115)
1
0x16 (22)
148 float
RWES
[C;;oFs]
[C.oFS]
Current (1)
Current Offset
Calibrate the current
reading with an off-
set value.
-9,999.000 to 9,999.000 0.0 Always Instance 1
Map 1 Map 2
1140 1380
0x73 (115)
1
0xB (11)
149 float
RWES
[`C;;Si]
[ C.Si]
Current (1)
Output Source In-
stance
Select which output
instance the current
transformer will
monitor.
1 to 12 1 Always Instance 1
Map 1 Map 2
1156 1396
0x73 (115)
1
0x13 (19)
150 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other
interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set