PM Integrated Controller 74 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[`A;Sd]
[ A.Sd]
Alarm (1 to 4)
Sides
Select which side or
sides will trigger this
alarm.
[both] Both (13)
[high] High (37)
[LoW] Low (53)
Both Type is not
set to Off.
Instance 1
Map 1 Map 2
1486 1886
Offset to next
instance (Map
1 equals +50,
for Map 2
equals +60)
0x6D (109)
1 to 4
4
26 uint
RWES
[`A;LA]
[ A.LA]
Alarm (1 to 4)
Latching
Turn alarm latching
on or off. A latched
alarm has to be
turned off by the
user.
[nLAt] Non-Latching (60)
[`LAt] Latching (49)
Non-
Latching
Type is not
set to Off.
Instance 1
Map 1 Map 2
1492 1892
Offset to next
instance (Map
1 equals +50,
for Map 2
equals +60)
0x6D (109)
1 to 4
7
27 uint
RWES
[`A;bL]
[ A.bL]
Alarm (1 to 4)
Blocking
Select when an
alarm will be
blocked. After start-
up and/or after the
set point changes,
the alarm will be
blocked until the pro-
cess value enters the
normal range.
[`oFF] Off (62)
[`Str] Startup (88)
[StPt] Set Point (85)
[both] Both (13)
Off Type is not
set to Off.
Instance 1
Map 1 Map 2
1494 1894
Offset to next
instance (Map
1 equals +50,
for Map 2
equals +60)
0x6D (109)
1 to 4
8
28 uint
RWES
[`A;Si]
[ A.Si]
Alarm (1 to 4)
Silencing
Turn alarm silencing
on to allow the user
to disable this alarm.
[`oFF] Off (62)
[``on] On (63)
Off Type is not
set to Off.
Instance 1
Map 1 Map 2
1490 1890
Offset to next
instance (Map
1 equals +50,
for Map 2
equals +60)
0x6D (109)
1 to 4
6
29 uint
RWES
[A;dSP]
[A.dSP]
Alarm (1 to 4)
Display
Display an alarm
message when an
alarm is active.
[`oFF] Off (62)
[``on] On (63)
On Type is not
set to Off.
Instance 1
Map 1 Map 2
1510 1910
Offset to next
instance (Map
1 equals +50,
for Map 2
equals +60)
0x6D (109)
1 to 4
0x10 (16)
30 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other
interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set