Watlow EZ-ZONE
®
PM Integrated Controller • 73 • Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[`o;CA]
[ o.CA]
Output (1 or 3 pro-
cess)
Calibration Offset
Set an offset value
for a process output.
-1,999.000to9,999.000°For
units
-1,110.555to5,555.000°C
0.0°For
units
0.0°C
Always if
digit 6 or
10 of part
number is
an "F".
Instance 1
Map 1 Map 2
732 852
Instance 2
Map 1 Map 2
812 932
0x76 (118)
1 or 3
7
105 float
RWES
[Alm]
[`Set]
Alarm Menu
[`A;ty]
[ A.ty]
Alarm (1 to 4)
Type
Select whether the
alarm trigger is a
fixed value or will
track the set point.
[`oFF] Off (62)
[PR;AL] Process Alarm (76)
[dE;AL] Deviation Alarm (24)
Off Always Instance 1
Map 1 Map 2
1508 1908
Offset to next
instance (Map
1 & Map 2)
equals +60
0x6D (109)
1 to 4
0xF (15)
20 uint
RWES
[`Sr;A]
[ Sr.A]
Alarm (1 to 4)
Source Function A
Select what will trig-
ger this alarm.
[``Ai] Analog Input (142)
[PWr] Power, Control Loop
(73)
[``Pu] Process Value (241)
[`Lnr] Linearization (238)
[CUrr] Current (22)
Type is not
set to Off
or devia-
tion..
Instance 1
Map 1 Map 2
1512 1912
Offset to next
instance (Map
1 & Map 2)
equals +60
0x6D (109)
1 to 4
0x11 (17)
21 uint
RWES
[`is;A]
[ iS.A]
Alarm (1 to 2)
Source Instance A
Set the instance of
the function selected
above.
1 or 2 1 Type is not
set to Off.
Instance 1
Map 1 Map 2
1514 1914
Instance 2
Map 1 Map 2
1564 1974
0x6D (109)
1 to 2
0x12 (18)
22 uint
RWES
[`A;hy]
[ A.hy]
Alarm (1 to 4)
Hysteresis
Set the hysteresis for
an alarm. This deter-
mines how far into
the safe region the
process value needs
to move before the
alarm can be cleared.
0.001to9,999.000°Forunits
0.001to5,555.000°C
1.0°For
units
1.0°C
Type is not
set to Off.
Instance 1
Map 1 Map 2
1484 1884
Offset to next
instance (Map
1 equals +50,
for Map 2
equals +60)
0x6D (109)
1 to 4
3
24 float
RWES
[`A;Lg]
[ A.Lg]
Alarm (1 to 4)
Logic
Select what the out-
put condition will
be during the alarm
state.
[`AL;C] Close On Alarm (17)
[`AL;o] Open On Alarm (66)
Close On
Alarm
Type is not
set to Off.
Instance 1
Map 1 Map 2
1488 1888
Offset to next
instance (Map
1 equals +50,
for Map 2
equals +60)
0x6D (109)
1 to 4
5
25 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other
interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set