Loading...
Watlow EZ-ZONE
®
PM Integrated Controller 79 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[``Fn]
[ Fn]
Function Key (1 to 2)
Digital Input Func-
tion
Program the EZ Key
to trigger an action.
Functions respond to
a level state change
or an edge level
change.
[none] None (61)
[P;StS] Profile Start/Stop,
level triggered (208)
[ProF] Profile Start Number,
edge triggered (196)
[P;hoL] Profile Hold/Resume,
level triggered (207)
[P;diS] Profile Disable, level
triggered (206)
[`t;da] TRU-TUNE+
®
Dis-
able, level triggered (219)
[`oFF] Control Outputs Off,
level triggered (90)
[MAn] Manual/Auto Mode,
level triggered (54)
[tUnE] Tune, edge triggered
(98)
[idLE] Idle Set Point Enable,
level triggered (107)
[`F;AL] Force Alarm, level
triggered (218)
[`AoF] Alarm Outputs &
Control Loop Off, level trig-
gered (220)
[`SiL] Silence Alarms, edge
triggered (108)
[ALM] Alarm Reset, edge
triggered (6)
[P;LoC] Lock Keypad, level
triggered (217)
[usr;r] Restore User Set-
tings, edge triggered (227)
[LMr] Limit Reset, edge
triggered (82)
None Always Instance 1
Map 1 Map 2
1324 1564
Instance 2
Map 1 Map 2
1344 1584
0x6E (110)
1 to 2
3
138 uint
RWES
[``Fi]
[ Fi]
Function Key (1 to 2)
Instance
Select which instance
the EZ Key will
affect. If only one
instance is available,
any selection will af-
fect it.
1 to 4 0 Always Instance 1
Map 1 Map 2
1326 1566
Instance 2
Map 1 Map 2
1346 1586
0x96 (110)
1 to 2
4
139 - - - -
[gLbL]
[`Set]
Global Menu
[`C_F]
[ C_F]
Global Menu
Display Units
Select which scale to
use for temperature.
[```F]°F(30)
[```C]°C(15)
°F Always - - - - - - - - 110
- - - -
[AC;LF]
[AC.LF]
Global Menu
AC Line Frequency
Set the frequency to
the applied ac line
power source.
[``50] 50 Hz (3)
[``60] 60 Hz (4)
60 Hz Always Instance 1
Map 1 Map 2
886 1006
0x6A (106)
1
4
89 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other
interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set