FILENAME
DATE:
B. CREWS
DESCRIPTION:
PAGE
DRAWN BY:
Duct Temperature Sensor
1
JOB NAME
07/13/15
G-DUCSENS1.CDR
OE230 & OE231
Duct Temperature Sensors
OE230 (6" Probe) & OE231 (12" Probe)
Mounting Plate
Gasket
Adhesive Backed Drill Guide
Mounting Template
11-1/2" (OE231)
5-1/2" (OE230)
Mounting Plate
4.0"
3/4"
1/4" Hex Head Sheet Metal Screws
Thread
Together
Duct Work
Drill 3/8” Hole In Ductwork For Probe
Leads Are Non-polarized.
Butt Splice Leads To 24 Gauge
Wire Minimum. Connect Leads
To "Analog In" And "Ground"
At Controller.
Notes:
1.)All Wiring To Be In Accordance With
Local And National Electrical Codes
And Specifications.
Temperature Sensor Resistance/Voltage Chart
Temp Resistance* Voltage
F Ohms @ Input*
-10.............93333........4.620
-5...............80531........4.550
0 ...............69822 ........4.474
5 ...............60552 ........4.390
10..............52500........4.297
15..............45902........4.200
20..............40147........4.095
25..............35165........3.982
30..............30805........3.862
35..............27140........3.737
40..............23874........3.605
°
Temp Resistance* Voltage
F Ohms @ Input*°
45..............21094........3.470
50..............18655........3.330
52..............17799........3.275
54..............16956........3.217
56..............16164........3.160
58..............15385........3.100
60..............14681........3.042
62..............14014........2.985
64..............13382........2.927
66..............12758........2.867
68..............12191........2.810
Temp Resistance* Voltage
F Ohms @ Input*°
69..............11906 ........2.780
70..............11652 ........2.752
71..............11379 ........2.722
72..............11136 ........2.695
73..............10878........2.665
74..............10625........2.635
75..............10398........2.607
76..............10158........2.570
78..............9711 ..........2.520
80..............9302..........2.465
82..............8893..........2.407
Temp Resistance* Voltage
F Ohms @ Input*
84..............8514..........2.352
86..............8153..........2.297
88..............7805..........2.242
90..............7472..........2.187
95..............6716..........2.055
100............6047..........1.927
105............5453..........1.805
110 ............4923..........1.687
115 ............4449..........1.575
120............4030..........1.469
°
125............3656..........1.369
*Chart Notes:
1. Use the resistance column to check the thermistor sensor while disconnected from the controllers (not powered).
2. Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DC volts.
Place the "-"(minus) lead on GND terminal and the "+"(plus) lead on the sensor input terminal being investigated. If the voltage
is above 5.08 VDC, the sensor or wiring is "open." If the voltage is less than 0.05 VDC, the sensor or wiring is shorted.
The Duct Sensor Is Used For Sensing Supply
Or Return Air Temperatures. Location Of The
Sensors Is Very Important In Order To Obtain
Accurate Temperature Readings. The
Following Recommendations Should Be
Followed:
When Used As A Supply Air Sensor The
Sensor Should Be Mounted In The Supply Air
Duct As Close To The HVAC Unit As Possible
And Upstream Of The Bypass Damper (If
Used) For Best Results. For Best Accuracy,
Apply Insulation On The Outside Of The
Ductwork Over The Sensor. This Will Help
Thermal Gradients From Affecting The Sensor.
Supply Air
Return Air
When Used As A Return Air Sensor The
Sensor Should Be Mounted In The Return Air
Duct As Close To The HVAC Unit As Possible
And Upstream Of The Bypass Damper (If
Used) For Best Results. For Best Accuracy,
Apply Insulation On The Outside Of The
Ductwork Over The Sensor. This Will Help
Thermal Gradients From Affecting The Sensor.
See The Systems Installation And Operation
Manual For Other Design Considerations And
Recommendations Regarding Duct
Temperature Sensor Location.
Caution!
Technical Specifications
Sensor Element:
Type III Thermistor 10k ohm @ 77ºF
Accuracy:
± 0.4º F between 40º F to 95º F
Range:
-30º F to 150º F
Question and Answer IconNeed help?

Do you have a question about the WattMaster OE230 and is the answer not in the manual?

Summary

Duct Temperature Sensors OE230 & OE231

Usage and Installation Guidance

Covers safety precautions, supply and return air mounting.

Technical Specifications

Lists sensor parameters like element type, accuracy, and range.

Data Chart and Notes

Explains resistance/voltage readings and general installation notes.

OE291 Thermowell Assembly

Water Temperature Sensing

Details for mounting in entering and leaving water lines.

Technical Specifications

Lists sensor parameters like element type, accuracy, and range.

Data Chart and Notes

Explains resistance/voltage readings and general installation notes.

Strap-On Temperature Sensor Kit OE233

Installation Instructions

Step-by-step guide for mounting and wiring the sensor kit.

Mounting Considerations

Important notes for accurate readings and proper installation.

Outside Air Sensor OE250

Installation and Safety

Warnings for handling, mounting, and wiring.

Technical Specifications

Lists sensor parameters like element type, accuracy, and range.

Data Chart and Notes

Explains resistance/voltage readings and general installation notes.

Space Humidity Sensor OE265-11

Installation Instructions

Steps for mounting and wiring the humidity sensor.

Mounting Considerations

Advice on sensor placement for optimal performance.

Wall Mounted Humidity Sensor

Wiring and Data Charts

Sensor connections, RH/Voltage conversion chart, and notes.

Outside Air Humidity Sensor OE265-13

Installation and Mounting

Guidance for mounting and wiring the sensor.

Technical Data

Specifications including sensor element, range, accuracy, and weight.

Outside Air Humidity Sensor Data

Wiring Diagram and Charts

Sensor connections, RH/Voltage chart, and notes.

Return Air Humidity Sensor OE265-14

Installation and Mounting

Guidance for mounting and wiring the sensor.

Technical Data

Specifications including sensor element, range, accuracy, and weight.

Return Air Humidity Sensor Data

Wiring Diagram and Charts

Sensor connections, RH/Voltage chart, and notes.

Airflow Sensor OE271

Specifications and Warnings

Technical data, pressure range, and safety warnings.

Mounting Information

Installation for duct static pressure and VAV applications.

Airflow Sensor OE274

Specifications and Warnings

Technical data, pressure range, and safety warnings.

Installation Notes

Mounting and wiring guidance for the airflow sensor.

Room Sensors OE210-OE213

Dimensions and Specifications

Typical dimensions, resistance/voltage chart, and caution notes.

Caution and Chart Notes

Important handling advice and explanations for sensor readings.

Static Pressure Pickup Tube OE290

Installation and Safety

Cautionary advice and installation notes for the pickup tube.

Digital Room Sensor OE217-02 & OE217-03

Description and Features

Details sensor capabilities, display, and functions.

Mounting and Specifications

Instructions for mounting and technical sensor data.

Digital Room Sensor OE217-04

Description and Features

Details sensor capabilities without a display.

Mounting and Specifications

Instructions for mounting and technical sensor data.

Wall Mounted CO2 Sensor OE256-05

Description and Applications

Details sensor features, technology, and typical applications.

Mounting and Specifications

Instructions for mounting and technical sensor data.

Duct Mounted CO2 Sensor OE256-07

Description and Applications

Details sensor features, technology, and typical applications.

Mounting and Specifications

Instructions for mounting and technical sensor data.

Building Static Pressure Sensor OE258-01

Description and Specifications

Details sensor features, case material, and technical data.

Suction Pressure Transducer Kit OE275-03

Description and Specifications

Details kit components, function, and transducer specifications.

E-BUS Digital Sensor Cable Assembly

Description and Specifications

Details cable features, types, and technical data.

E-BUS Adapter Hub HZ-EBC-248

Description and Specifications

Details hub function, connectivity, and technical data.

E-BUS Adapter Hub MS000248

Description and Specifications

Details hub function, connectivity, and technical data.

WattMaster OE230 Specifications

General IconGeneral
CategoryAccessories
Voltage230V
Frequency50/60Hz
MaterialPlastic
Input Voltage230VAC
Output Voltage230VAC
ProtectionOvervoltage