CHAPTER 8 – WATER HEATER MANAGEMENT
OMM-0143_A • GF-216 • 9/6/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 120 of 170
WHM Client screen WHM Manager screen
Figure 8.6-4: Operating Controls: Sequencing Controls Screens
TABLE 8-6e: Operating Controls → Anti-Cycling Parameters
Available Choices or Limits
The minimum length of time a unit must stay off after shutting down or going into standby.
Once Slow Shutdown is enabled on a unit, if the unit is run at a fire rate above Off Delay
Threshold and then shuts down, the fire rate will be reduced to the Stop Level for a period of
time defined in Off Delay. This feature prevents units running at high fire rates from being
quickly turned off and flushed with cold water, thereby possibly damaging the heat exchanger.
Specifies the amount of time the full shut down will be delayed when Slow Shutdown is
enabled
The threshold fire rate above which the Slow Shutdown feature will take effect
Specifies the temperature above setpoint the unit may rise to during delay shutdown.
Offset temperature from setpoint before a unit may come online.