Innovation - Edge [i] Installation, Operation, Maintenance Manual
CHAPTER 3 – OPERATION
OMM-0143_A • GF-216 • 9/6/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 46 of 170
The maximum address in the WHM cascade (1 to 16,
WHM Unit Mode = WHM Manager).
The communication baud rate in the cascade.
The timeout before a Modbus Fault is declared (5 to 999
sec.).
The number of Modbus Comm errors allowed before
invoking a Modbus comm fault (1 to 9).
The number of comm errors on ports 1 - 8.
The number of comm errors on ports 9 – 16..
The Client/Client Device address (0 to 250).
Choose either Points or Degrees (WHM Unit Mode =
WHM Manager).
The unit or plant’s operating mode if communication is
lost: Shutdown or Constant Setpoint.
Unit/Plant Failsafe Setpoint
The unit or plant’s setpoint if communication is lost (Unit
Failsafe Mode = Constant Setpoint).
If Enabled, all Client units in the Cascade will
synchronize time and date with the WHM Manager
(WHM Unit Mode = WHM Manager).
The minimum number of units in the WHM cascade (1 to
16, WHM Unit Mode = WHM Manager).
The maximum number of units in the WHM cascade (1 to
16, WHM Unit Mode = WHM Manager).
Specifies the time the WHM Manager must wait for a
backup Client unit to turn on (15 – 300, WHM Unit Mode
= WHM Manager).
Main Menu → Advanced Setup → WHM Cascade → WHM Application Configuration
The WHM Cascade’s application: DHW.
The WHM Cascade’s operating mode, Constant
Setpoint.
The WHM Cascade’s Setpoint (Operating Mode =
Constant Setpoint).
Main Menu → Advanced Setup → WHM Cascade → Operating Controls
Main Menu → Advanced Setup → WHM Cascade → Operating Controls → Sequencing Controls
Choose Off, On - Outlet Temp or On - Avg Temp. If
either “On” option is chosen, and WHM detect a “low-
flow” condition, it slowly shuts down one unit at a time in
an attempt to raise the Fire Rate of the remaining units.
Specifies the valve position below which the plant enters
this mode (10% to 35%).
The valve position that triggers the next unit to come on
line.
The valve position that triggers the next unit to go off
line.
The maximum number of units that will fire (WHM Unit
Mode = WHM Manager).
The time an open Isolation Valve will remain open once
a unit cycles off (WHM Unit Mode = WHM Manager).
Controls the frequency of updates made to the Fire Rate
sent to all units.
Main Menu → Advanced Setup → WHM Cascade → Operating Controls → Anti-Cycling Control
Minimum length of time a unit must stay off after shutting
down/going standby (30 to 300 sec.).
Once enabled, if the unit runs at a fire rate above Off
Delay Threshold and then shuts down, the fire rate will
be reduced to the Stop Level for a period of time defined
in Off Delay.