Innovation - Edge [i] Installation, Operation, Maintenance Manual
CHAPTER 3 – OPERATION
OMM-0143_A • GF-216 • 9/6/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 47 of 170
Specifies the amount of time full shut down will be
delayed (Slow Shutdown = Enabled).
The threshold fire rate above which Slow Shutdown will
take effect (Slow Shutdown = Enabled).
The temperature above setpoint the unit may rise to
during delay shutdown (0 to 25°F).
Offset temperature from setpoint before a unit may come
online (0 to 25°F).
Main Menu → Advanced Setup → WHM Cascade → Operating Controls → Valve Configuration
Select the output signal type of the selected output:
Current or Voltage.
Choose Enabled or Disabled.
Displays the selected valve’s current status (Valve
Feedback = Enabled).
Main Menu → Advanced Setup → WHM Cascade → Operating Controls → Lead/Lag
Select: Run Hours, Unit Size or Select Lead Lag.
The number of hours after which the Lead unit is rotated
(25 – 225, Lead/Lag Setting = Run Hours)
Specify the address of the Lead unit (0 to 127,
(Lead/Lag Setting = Select Lead Lag).
Specify the address of the Lag unit (0 to 127, Lead/Lag
Setting = Select Lead Lag).
3.3.4.3 Main Menu → Advanced Setup → Com & Network
Main Menu → Advanced Setup → Comm & Network → BAS
To enable communication with a BAS, select Off or
Modbus TCP.
Specify the network address of the Edge Controller on the
BAS network (0 – 127, BAS = Modbus TCP).
Displays the local IP address of the Edge Controller (BAS
= Modbus TCP).
Displays the status of BAS communications.
Choose: Fahrenheit or Celsius (BAS = Modbus TCP)
Set to Enabled to enable BAS security (BAS = Modbus
TCP).
Specifies the IP address of the BAS server (Security =
Enabled).
Specifies the MAC address of the BAS server (Security =
Enabled).
Main Menu → Advanced Setup → Comm & Network → onAER
To enable onAER, select the communication method:
Ethernet, Wi-Fi or Wiznet (for units where the Edge
Controller replaced a C-More).
Determines how frequently unit data is uploaded to the
server (30 to 9999 sec.).
Determines how cascade data is uploaded to the server
(60 to 9999 sec.).
The communication interface status.
Main Menu → Advanced Setup → Comm & Network → Ethernet
Enables/disables DHCP (Dynamic Host Configuration
Protocol).
The static IP address of the unit (DHCP = Disabled).