Innovation - Edge [i] Installation, Operation, Maintenance Manual
CHAPTER 3 – OPERATION
OMM-0143_A • GF-216 • 9/6/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 48 of 170
The subnet address of the network (DHCP = Disabled).
The IP address of the Gateway (DHCP = Disabled).
The IP address of DNS Server 1 (DHCP = Disabled).
(The IP address of DNS Server 2 DHCP = Disabled).
Allows the unit to be pinged..
Main Menu → Advanced Setup → Comm & Network → Communication Failsafe
Choose how the unit will operate when either the Manager
communication or a Remote Signal is lost: Constant Setpt
or Shutdown.
The unit’s default setpoint when communication fails (60 to
160°F, Unit Failsafe Mode = Constant Setpt).
3.3.4.4 Main Menu → Advanced Setup → Ancillary Devices
Main Menu → Advanced Setup → Ancillary Device → Interlocks
Choose the Remote Interlock: Flow, Damper, Louver,
Other.
Specify what will shut down if the selected Remote
Interlock is open: Unit Shutdown or Sys Shutdown.
Choose the Delayed Interlock: Valve 1, Valve 2, Louver 1
or Louver 2.
Select the Delayed Interlock’s delay (0 to 240 sec.).
3.3.4.5 Main Menu → Advanced Setup → Performance
Main Menu → Advanced Setup → Performance → Temperature Control
Main Menu → Advanced Setup → Performance → Temperature Control → PID Setting
Generates a fire rate based on the error that exists
between the setpoint and the actual outlet temperature. If
the error is less than Proportional Band, fire rate will be
less than 100%. If the error is equal to or greater than
proportional band, the fire rate will = 100% (1°F to 120°F).
Specifies the fraction of the output, due to setpoint error, to
add or subtract from the output each minute to move
towards the setpoint. (0.00 to 5.00)
Specifies the time that this action advances the output; it
responds to the rate of change of the setpoint error (0.00 to
2.00 min.).
These three parameters eliminate Temperature
Overshoots during the “Warmup” period of a cold ignition
cycle by temporarily modifying the PID Gain parameter
during warmup.
Choose Yes to reset all parameters to the factory default.
Main Menu → Advanced Setup → Performance → Temperature Control → Temperature Conformance
These two settings create an “outlet temperature zone”
(between Active Setpoint + Deadband High and Active
Setpoint – Deadband Low) in which no Valve Position
corrections are attempted. (0 to 25°F for both)
The unit’s maximum allowable working temperature. If the
unit reaches this limit, it will fault and shut down (40 to 210
°F).