Innovation - Edge [i] Installation, Operation, Maintenance Manual
CHAPTER 3 – OPERATION
OMM-0143_A • GF-216 • 9/6/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 49 of 170
Main Menu → Advanced Setup → Performance → Temperature Control → Setpoint Range
Determines the upper and lower limit within which the
setpoint can vary.
Enables/disables Setpoint Limiting functionality.
Sets the number of °F below Setpoint High Limit the
unit’s outlet temperature must fall before the unit restarts (0
to 10°F, Setpoint Limiting = Enable).
Enables/disables Setback Schedule functionality
The Setpoint that will be in effect during the Setback
period. (60°F to 245°F, Setback Schedule = Enabled).
The Setback period’s start time (Setback Schedule =
Enable).
The Setback period’s end time (Setback Schedule =
Enable).
Main Menu → Advanced Setup → Performance → Temperature Control → FFWD Settings
Displays the current FFWD temperature.
Displays the calculated PID output.
Displays the current FFWD output.
Adjusts the output by adding an offset to the breakpoint
chart at minimum flow. This is used to fine tune Feed-
Forward (FFWD) output at low flow levels. (-50 - +50°F)
Adjusts the output by changing the scaling of the
breakpoint chart at maximum flow. (-50 - +50°F)
Enables Outlet Feedback functionality.
The percentage of feedback from the water outlet sensor
the algorithm factors to determine fire rate (0.01 – 1.00).
The Feedback start position (0 – 100%).
The Feedback end position (0 – 100%).
Specifies the maximum Feedback position (0 – 100%).
Displays the current feedback value.
Breakpt at 100 to
Breakpt at 0
Allows breakpoint temperature settings to be entered for
100% to 0% in 10% increments (60 – 260°F).
Enables temperature governor limiting functionality, which
aggressively reduces the effective Fire Rate as the Outlet
Temperature approaches the High Temperature Limit.
GOV Limit-5 – GOV Limit-15
When the Outlet Temperature exceeds the Temperature
Hi Limit by 5 to 15°F, the effective Fire Rate will be
reduced by the value entered in GOV Limit-5 through GOV
Limit-15 (0 – 100°F).
If the inlet water temp is above 70F, algorithm adds offset
provided by this item to all the 11 breakpoints (“breakpoint
at 100” – “breakpoint at 0”). (-10 - +10°F)
If the inlet water temp is below 70F, algorithm adds offset
provided by this item to all the 11 breakpoints (“breakpoint
at 100” – “breakpoint at 0”). (-10 - +10°F)
No Feed Forward above this fire rate
No Feed Forward above fire rate feature status
Menu → Advanced Setup → Performance → Fire Control
Main Menu → Advanced Setup → Performance → Fire Control → Purge Control
Sets the blower speed (blower output voltage) during the
Purge cycle (2.0 to 10.0 V).