Innovation - Edge [i] Installation, Operation, Maintenance Manual
CHAPTER 3 – OPERATION
OMM-0143_A • GF-216 • 9/6/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 50 of 170
Allows adjustment of the pre-ignition purge time (5 to 60
sec.).
Allows adjustment of the post purge time before the unit
shuts down (0 to 60 sec.).
Main Menu → Advanced Setup → Performance → Fire Control → Ignition Control
Sets the air fuel valve position at which the unit will operate
during the ignition sequence (5% to 60%).
Displays the actual blower voltage during ignition.
Allows an adjustment to the blower voltage during ignition
(-5.00 to 5.00).
Specifies how long to remain in the low fire position after
ignition, before going to the desired output (2 to 600 sec.).
Sets the length of time the unit stays in ignition position (0
to 60 sec.).
Displays the maximum time between confirmation of gas
valve opening (POC) and a stable flame detected.
Main Menu → Advanced Setup → Performance → Fire Control → Operating Control
Specifies the valve position at Start Level (0 to 40%).
Specifies the valve position at Stop Level (0 to 40%).
The maximum valve position for unit (40 to 100%).
Specifies the blower voltage in Standby Mode, during
which the blower motor remains “ON” at low speed, to limit
power cycles. AERCO recommends keeping the default,
however, may set this between 2.00 and 0 volts on
individually vented units in positive pressure mechanical
rooms to compensate (0.0 to 10.0V).
Defines the rate at which the valve position will progress
from one step to the next (0.5 to 60 sec.).
Together, these 3 parameters define an optional Fire Rate
the Controller will skip-over (Skip Range Cntr = center of
the range). These can be used to reduce objectionable
noise at a certain Fire Rate, if there is no other remedy.
Main Menu → Advanced Setup → Performance → Fire Control → Anti-Cycling Control
Sets the minimum time a unit must stay off after shutting
down or going into standby (0 to 600 sec.).
Enable/disable the slow shut down feature once Off Delay
threshold is achieved.
Defines a Shutoff delay, during which time the unit remains
at minimum fire rate after the unit has sequenced to
shutoff. It is activated only when Off Delay Threshold is
reached (0 to 9999 secs). (Slow Shutdown = Enabled).
The Fire rate that activates the Off Delay function
(40 to 100 %). (Slow Shutdown = Enabled).
Specifies the number of degrees above setpoint that the
outlet temperature can rise without triggering a unit shut
down (0 to 25°F).
The temperature offset from setpoint before a unit may
come online. (0°F to 25°F). This can reduce excessive
cycling in AUTO mode. When above 0, the unit will not turn
on again until Valve Position In reaches the Start Level
value AND the outlet temperature goes below Demand
Offset; the unit will fire at the ignition valve position or
below for 1 minute. If this entry equals 0, the unit will turn
on when the Valve Position In = Start Level.