Programming Classic Unit
12
3.3 Programming level 3 at 15 °C, Classic Card TCC 5.25
Display Setting Default Min Max Unit
0 Cut-out value for low voltage 195 160 210 Volt
1 Remote control activated/deactivated 0 0 1
2 Choice of blower type
0 = blower speed regulated
1 = blower speed uninterrupted
101
3 Choice of thermostatic regulation or permanent ventilation 1 0 1
4 Choice of internal/external air temperature sensor 0 0 1
5 Choice of temperature reading in °C or °F
0 = °C, 1 = °F
001
6 Calibration of blower speed 5 70 1 70
7 Calibration of blower speed 4 40 1 70
8 Calibration of blower speed 3 35 1 70
9 Calibration of blower speed 2 29 1 70
A Calibration of blower speed 1 23 1 70
b Access code for programming levels 64 0 99
C Duration of heat cycle in dehumidification mode 1 1 99 minutes
D Duration of cool cycle in dehumidification mode 1 1 99 minutes