Programming Premium Unit
8
2 Programming Premium Unit
2.1 Programming level 2, Premium Card TECC 4.25
Display Setting Default Min Max Unit
b Selection of blower speed A 0 A
H Water temperature
F Selection of function mode 3 1 5
Cool Only F1
Heat Only F2
Automatic cooling/heating with reverse cycle F3
Automatic cooling/heating with external heater F4 *
Heat Only with external heater F5
U Reading of voltage supply 0 Volt
1C Choice compressor 1 ON/OFF 1 0 1
2C Choice compressor 2 ON/OFF 1 0 1
3C Choice compressor 3 ON/OFF 1 0 1
4C Choice compressor 4 ON/OFF 1 0 1
P Priority order for compressors 1-4 123
L Time delay between compressor starts 1-4 9 1 9 seconds
1L Switch off temperature delay for compressor 1 0 0 55 1/10°
2L Switch off temperature delay for compressor 2 0 0 55 1/10°
3L Switch off temperature delay for compressor 3 0 0 55 1/10°
4L Switch off temperature delay for compressor 4 0 0 55 1/10°
d Dehumidification cycle when system turned off (0 = non ac-
tive; 1 = 1 cycle per 24h; 2 = 2 cycles per 24h ; 3 = 3 cycles per
24h)
003
t Time to display table F 1 1 12 20 sec.
S Choice of chilled water temperature sensor outlet or inlet 1 0 2
c Temperature difference between compressor starts 15 0 99 1/10°
E Max temperature difference between chilled water outlet and
inlet
80 10 99 1/10°
* Water heater integration.