Installation and Connection
3-14 | CFW-11M G2
3
3. 2.1.4 Harmonics of the 6-Pulse Rectifier
Table 3.6 on page 3-14, Figure 3.16 on page 3-14 and Figure 3.17 on page 3-14 show the typical values of the
harmonic content of the currents, Power Factor (PF) and THD (I) on the power supply, considering the 6-pulse
rectifier.
Table 3.6: Individual harmonics, Power Factor and THD (I) typical for rated load in the output, 6-pulse rectifier
Harmonic
Order
I (%) FP THD(I)
1 100.0 %
0,89 42 %
5 38.7 %
7 14.1 %
11 6.7 %
13 3.3 %
17 2.9 %
19 1.9 %
23 1.4 %
Normalized Harmonic Amplitude
40 %
35 %
25 %
15 %
5 %
30 %
20 %
10 %
0 %
0 % 20 % 40 % 60 %
Load percentage
5th Harmonic
7th Harmonic
11th Harmonic
13th Harmonic
17th Harmonic
19th Harmonic
23th Harmonic
80 % 100 %
120 %
Note: Amplitude of the normalized harmonics as a function of the fundamental with 100 % of load. 6-pulse rectifier.
Figure 3.16: Typical values of the harmonics of the input current with variation of the output power