First Time Power-Up and Start-Up
5-4 | CFW-11M G2
5
Step Action/Result Display Indication Step Action/Result Display Indication
8 - At this point the Oriented
Start-up routine starts
and the "Config" status
is displayed at the top left
corner of the keypad
- The parameter "Language
P0201: English" is already
selected
- If needed, change the
language by pressing
"Select".Then, press
or to scroll
through the available options
and press "Save" to select a
different language
Config
LOC
0rpm
Reset 13:48 Selec.
Idioma
P0201: Portugues
Tipo de Controle
P0202: V/F 60 HZ
18 - This parameter will only be
visible if the encoder board
ENC1 is installed in the
inverter
- If there is an encoder
connected to the motor,
set P0405 according to the
encoder pulses number. To
do so, press "Select"
Config
LOC
0rpm
Reset 13:48 Selec.
Potencia Nom. Motor
P0404: 30hp 22kW
Numero Pulsos Encoder
P0405: 1024 ppr
9 - If needed, change the value
of P0202 according to the
type of control. To do so,
press "Select"
- The settings listed here
are valid only for P0202 =
0 (V/f 60 Hz) or P0202 = 1
(V/f 50 Hz). For other options
(Adjustable V/f, VVW, or
Vector modes), please
refer to the programming
manualulte o manual de
programação
Config
LOC
0rpm
Reset 13:48 Selec.
Idioma
P0201: Portugues
Tipo de Controle
P0202: V/F 60 HZ
19 - If needed, set P0406
according to the motor
ventilation. To do so, press
"Select"
- To complete the Oriented
Start-up routine, press
"Reset" (left soft key) or
Config
LOC
0rpm
Reset 13:48 Selec.
Numero Pulsos Encoder P0405:
1024 ppr
Ventilacao do Motor
P0406: Autoventilado
10 - If needed, change the value
of P0296 according to the
line rated voltage
To do so, press "Select"
This modification will affect
P0151, P0153, P0185,
P0321, P0322, P0323, and
P0400
Config
LOC
0rpm
Reset 13:48 Selec.
Tipo de Controle
P0202: V/F 50 HZ
Tensao Nominal Rede
P0296: 500 - 525 V
20 - After few seconds, the
display returns to the
monitoring mode
Ready
LOC
0rpm
13:48 Menu
0 rpm
0.0 A
0.0 Hz
Figure 5.2: Oriented start-up
5.2.3 Setting of the Basic Application Parameters
After running the Oriented Start-up routine and properly setting the parameters, the inverter is ready to operate
in the V/f mode.
The inverter has a series of other parameters that allow its adaptation to different applications. This manual contains
some basic parameters whose setting is necessary in most cases. In order to simplify this task, there is a group
called Basic Application. To set the parameters contained in the Basic Application group, follow the sequence of
Figure 5.6 on page 5-11. For further details, refer to the programming manual of the CFW-11.
After the setting of those parameters, the start-up in the V/f mode will be completed.