Parâmetros de Leitura
CFW501 | 15-5
15
P0030 – Heatsink Temperature
Adjustable
Range:
-20 to 150 ºC Factory
Setting:
Properties: ro
Access groups
via HMI:
READ
Description:
Temperature in ºC measured inside the power module by the internal NTC.
P0037 – Motor Overload Ixt
Refer to section 14.1 MOTOR OVERLOAD PROTECTION (F0072 AND A0046) on page 14-1.
P0042 – Powered Time
Adjustable
Range:
0 to 65535 h Factory
Setting:
Properties: ro
Access groups
via HMI:
READ
Description:
It indicates the total number of hours that the inverter remained powered.
This value is kept even when power is removed from the inverter.
P0043 – Enabled Time
Adjustable
Range:
0.0 to 6553.5 h Factory
Setting:
Properties: ro
Access groups
via HMI:
READ
Description:
It indicates the total number of hours that the inverter remained enabled.
It indicates up to 6553.5 hours, and then it gets back to zero.
By setting P0204 = 3, the value of the parameter P0043 is reset to zero.
This value is kept even when power is removed from the inverter.