60 | Flameproof motors
TROUBLESHOOTING CHART
This troubleshooting chart provides a basic list of unusual cases that may occur during motor
operation, possible causes and recommended corrective actions. For further information,
contact WEG Service Area.
Table 10-1 - Basic listing of abnormalities, causes and corrective actions
Motor does not start either
coupled or uncoupled to the
load.
At least two power supply cables are interrupted,
without voltage;
Check the command panel, the power
supply cables and the terminals;
Motor starts with no load, but
fails when load is applied.
Motor starts very slowly and
doesn’t reach rated speed.
Load torque very high during starting;
Don’t apply load on the driven machine on
starting;
Very low power supply voltage;
Measure the power supply voltage, set the
correct value;
Very high voltage drop on the power supply
cables;
Check the installation design (transformer,
cable section, check relays, circuit breakers,
etc.);
Rotor with interrupted bars;
Check and repair the rotor bars, test the
short-circuit device (rings);
The power supply cable was interrupted after
starting;
Check the power supply cables;
Excessive no load current.
Very high power supply voltage;
Measure the power supply voltage and set it
to the correct value;
Heating on the stator winding.
Short-circuit among turns;
Interruption of parallel wires or winding phases of
the stator;
Stator winding becomes very
hot under load
Insufficient cooling due to dirty air channels;
Open and clean the air channels;
Fans operating in the wrong direction;
Correct the rotation direction of the fans;
Measure the stator current, decrease the
load and analyze the motor application;
High number of starts or very high moment of
inertia;
Reduce the number of starts;
Very high voltage, leading to iron losses are very
high;
Don’t exceed the rated voltage by 110%
except when specified on the nameplate;
Very low voltage, leading to current is very high;
Check the power supply voltage and the
motor voltage drop;
Interruption on a power supply cable or on
winding phase;
Measure the current in all phases and
correct it;
Rotor drags against the stator;
Check the air-gap, operation conditions
(vibration...), bearing conditions;
The operating condition doesn’t correspond to
the nameplate data;
Maintain the operation condition according
to the nameplate or reduce the load;
Power supply unbalance (burnt fuse, wrong
control);
Check if there is voltage unbalance or
operation
with two phases and correct it;