1066540000/00/02.09 103
896549 (ACT20X-HUI-SAO),
Terminal 21-22
Co Lo Lo/Ro
Uo, Voc 8.3 V IIC or A, B 7 µF 100 mH 10 mH/
Io, Isc 0.2 mA IIB or C, E, F 73 µF 100 mH 40 mH/
Po 0.4 mW IIA or D, G 1000 µF 100 mH 80 mH/
896549 (ACT20X-HUI-SAO),
Terminal 11, 12, 13, 14
Co Lo Lo/Ro
Uo, Voc 8.3 V IIC or A, B 7 µF 100 mH 1 mH/
Io, Isc 13.1 mA IIB or C, E, F 73 µF 100 mH 5 mH/
Po 27.3 mW IIA or D, G 1000 µF 100 mH 10 mH/
Terminal 21–22 / 21–23
U
i
: 30 V
I
i
: 120 mA
P
i
: 900 mW
C
i
: 3 nF
L
i
: 1 µH
Terminal (53, 54)
Status Relay: Non Hazardous location Zone 2 installation
Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC
Power max. 62.5 VA / 32 W 16 VA / 32 W
Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC
Terminal (43, 44)
Relay Output: Non Hazardous location Zone 2 installation
Voltage max. 250 V AC / 30 V DC 32 V AC / 30 V DC
Power max. 500 VA / 60 W 64 VA / 60 W
Current max. 2 A AC / 2 A DC 2 A AC / 2 A DC