Installation notes:
DANGER
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
WARNING
Substitution of components may impair intrinsic safety and/or suitability for Div.
2 / Zone 2.
The installation and wiring must be in accordance with the Canadian Electrical Code for Canada and
National Electrical Code NFPA 70, Article 500 or 505 for installation in USA.
For installation in Zone 2 or Division 2, the module must be installed in a suitable outer enclosure having an
IP protection of at least IP54.
The module is galvanically isolated and does not require grounding.
The module must be installed in pollution degree 2 or better.
In type of protection “intrinsic safety iD” the parameters for intrinsic safety for gas group II B are applicable.
Use 60/75 °C copper conductors in the wire size AWG: (26-14).