1066540000/00/02.09 89
896549 (ACT20X-HUI-SAO),
Terminal 21–23
Co Lo Lo/Ro
Uo 28 V IIC 80 nF
100 mH
4 mH/
Io 1.1 mA IIB 640 nF
100 mH
17 mH/
Po 0.80 W IIA 2.1 µF
100 mH
35 mH/
896549 (ACT20X-HUI-SAO),
Terminal 21–22
Co Lo Lo/Ro
Uo 8.3 V IIC 7 µF 100 mH 100 mH/
Io 0.2 mA IIB 73 nF 100 mH 400 mH/
Po 0.4 W IIA 1000 µF 100 mH 800 mH/
896549 (ACT20X-HUI-SAO),
Terminal 11, 12, 13, 14
Co Lo Lo/Ro
Uo 8.3 V IIC 7 µF 100 mH 1 mH/
Io 13.1 mA IIB 73 nF 100 mH 5 mH/
Po 27.3 mW IIA 1000 µF 100 mH 10 mH/
Terminal 21–22 / 21–23
U
i
: 30 V
I
i
: 120 mA
P
i
: 900 mW
C
i
: 3 nF
L
i
: 1 µF
Terminal (53, 54)
Status Relay: Non Hazardous location Zone 2 installation
Voltage max. 125 V AC / 110 V DC 32 V AC / 32 V DC
Power max. 62.5 VA / 32 W 16 VA / 32 W
Current max. 0.5 A AC / 0.3 A DC 0.5 A AC / 1 A DC
Terminal (43, 44)
Relay Output: Non Hazardous location Zone 2 installation
Voltage max. 250 V AC / 30 V DC 32 V AC / 30 V DC
Power max. 500 VA / 60 W 64 VA / 60 W
Current max. 2 A AC / 2 A DC 2 A AC / 2 A DC