4.5.4 3-point stepping controller (relay & relay)
ConF / Cntr: SP.Fn = 0 set-point controller
C.Fnc = 4 3-point stepping controller
C.Act = 0 inverse action
(e.g. heating applications)
ConF / Out.1: O.Act = 0 action Out.1 direct
Y.1 = 1 control output Y1 active
Y.2 = 0 control output Y2 not active
ConF / Out.2: O.Act = 0 action Out.2 direct
Y.1 = 0 control output Y1 not active
Y.2 = 1 control output Y2 active
PArA / Cntr: Pb1 = 1...9999 proportional band 1 (heating)
in units of phys. quantity (e.g. °C)
ti1 = 0,1...9999 integral time 1 (heating) in sec.
td1 = 0,1...9999 derivative time 1 (heating) in sec.
t1 = 0,4...9999 min. cycle time 1 (heating)
SH = 0...9999 neutral zone in units of phy. quantity
tP = 0,1...9999 min. pulse length in sec.
tt = 3...9999 actuator travel time in sec.
PArA / SEtP: SP.LO = -1999...9999 set-point limit low for Weff
SP.Hi = -1999...9999 set-point limit high for Weff
g
For direct action of the 3-point stepping controller, the controller output action
must be changed ( ConF / Cntr / C.Act = 1 ).
Configuration level
8800 process controller 55 Configuration examples
InH.1InL.1
SP.LO SP
SP.Hi
Out.1Â
InP.1Ê
Out.2
Â
100%
0%
100%
0%
PB1
SH
setpoint
output 1
process value
output 2