r chapter 11.1 (page 82)
Parameter setting level
8800 process controller 63 Parameters
Name Value range Description Default
t.F2
0,0...999,9
Filter time constant [s]
0,5
InP.3
Name Value range Description Default
InL.3
-1999...9999
Input value for the lower scaling point
0
OuL.3
-1999...9999
Displayed value for the lower scaling point
0
InH.3
-1999...9999
Input value for the upper scaling point
20
OuH.3
-1999...9999
Displayed value for the upper scaling point
20
t.F3
0,0...999,9
Filter time constant [s]
0,5
Etc.3
0...100 (°C)
32...212 (°F
External cold-junction reference temperature (external TC)
OFF
Lim
Name Value range Description Default
L.1
-1999...9999
Lower limit 1
-10
H.1
-1999...9999
Upper limit 1
10
HYS.1
0...9999
Hysteresis limit 1
1
dEl.1
0...9999
Alarm delay from limit value 1
0
L.2
-1999...9999
Lower limit 2 OFF
H.2
-1999...9999
Upper limit 2 OFF
HYS.2
0...9999
Hysteresis limit 2
1
dEl.2
0...9999
Alarm delay from limit value 2
0
L.3
-1999...9999
Lower limit 3
OFF
H.3
-1999...9999
Upper limit 3
OFF
HYS.3
0...9999
Hysteresis limit 3
1
dEl.3
0...9999
Alarm delay from limit value 3
0