BC
GENERATOR
RESISTANCE
FIGURES
CHECK
THE
RESISTANCE
OF
THE
EXCITER
WINDINGS··
SINGLE
EXCITER
CIRCUIT:
7.0
BCG
&
BCGA.
.......
1.9
ohm
DUAL
EXCITER
CIRCUIT:
7.0
BCG
.........................
2.5
ohm
CHECK
THE
CAPACITOR
SINGLE
EXCITER
CIRCUIT:
7.0
BCG
&
BCGA.
........
31.5
uF
±
DUAL
EXCITER
CIRCUIT
7.0
BCG
.........................
18.0
uF
±
CHECK
THE
ENGINES
SPEED
60
Hz
.60.5
-
61.5
50
Hz
50.5
-
51.5
·
ADJUST
THE
ENGINES
SPEED
BY
USING
THE
GOVERNORS
SPEED
ADJUSTMENT
TO
OBTAIN
THE
CORRECT
HERT2.
WESTERBEKE'S.
"AC
Electrical
Testing
&
Troubleshooting
Guide"
for
BC
Generators
is
availabfe
in
pdf
form.
Download
from
our
website:
¥J!MtJf!!..~eke,com..
LOAD
APPLIED
4-POLE
SPEED.
FREQUENCY
GENERATOR
(RPM)
(HERTZ)
120V
(110)
NONE
1830
..
62
122
(1530)
(52)
(112)
HALF
1800
60
120.
(1500)
(50)
(110)
FULL
1755
59.
I
110
(1455).
I
(49}
(100)
l
NOTE:
The
output
should
be
checked
periodically
to
ensure
proper
operation
of
the
generator
and
the
appliances
it
supplies.
If
an
AC
Voltmeter
or
Ampmeter
is
not
installed
to
monitor
the
voltage
and
load,
check
it
with
a
portable
meter
and
amp-probe.
VOLTAGE
230V
235
230
225