22 WIKA operating instructions pressure transmitter, models E-10 and E-11
EN
9. Specifications
Specications
Measuring range → See product label
Overpressure limit
bar Measuring ranges ≤ 16 bar 3 times
Measuring ranges ≥ 25 bar 2 times
Measuring range 1,000 bar 1.7 times
psi Measuring ranges ≤ 300 psi 3 times
Measuring range ≥ 500 psi 2 times
Measuring ranges 600, 1,000,
1,500, 10,000 psi
1.7 times
Measuring range 15,000 psi 1.43 times
bar abs., psi abs. 3.5 times
For oxygen version 2 times
Vacuum resistance Yes
Non-linearity per BFSL per
IEC 61298-2
≤ 0.2 % of span
Accuracy → See “Max. measuring deviation per IEC 61298-2”
Max. measuring deviation per
IEC 61298-2
0.5 % of span
Non-repeatability per IEC 61298-2 ≤ 0.1 % of span
Temperature error at 0 ... 80 °C [32 ... 176 °F]
Zero point ≤ 0.2 % of span/10 K
Span ≤ 0.2 % of span/10 K
Long-term stability per DIN 16086 ≤ 0.2 % of span/year
For use in hydrogen applications, observe the Technical information IN 00.40 at www.wika.com
regarding long-term stability.
Reference conditions Per IEC 61298-1
Output signal → See product label
9. Specications