EasyManua.ls Logo

Wilo Control SC2.0-Booster - Pump System Configuration

Wilo Control SC2.0-Booster
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
en
Installation and operating instructions • Wilo-Control SC2.0-Booster • Ed.01/2023-09 43
7.2.3.1 Menu system -> Pumps
Fig.87: Menu system -> Pumps menu item
Settings and data for the pumps used.
Fig.88: System→Pumps→Installation menu
item
Number of pumps installed in the system.
Maximum number of pumps running simultaneously.
The remaining pumps serve as standby pumps.
Fig.89: System→Pumps→Statistics 1/2
menu item
Running time data for the control device and the pumps.
Fig.90: System→Pumps→Statistics 2/2
menu item
Current speeds and calculated power for each pump.
Fig.91: System→Pumps→CAN fallback
menu item
The fallback setting in case of a communication problem between the control device and the
pump.
The setting determines the behaviour of the pump when the control device no longer per-
forms.
When “Stop” is selected, the pump is stopped.
When “Continue” is selected, the pump continues to operate in the n-c control mode at the
speed indicated below.
The speed can then be changed on the pump’s HMI. When communication with the control
device is re-established, the control device takes over control of the pump.