EasyManua.ls Logo

Window Master CompactSmoke WSC 320 - Page 19

Default Icon
27 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
19
X10
For connection of weather station.
Connection of wind / rain sensors type WLA 330 or rain sensor WLA 331.
Data
10.1 24V UPS (only available with Plus version)
10.2 Wind speed (only available with Plus version)
10.3 GND / 0V (only available with Plus version)
10.4 24V
10.5 Rain (10kΩ resistor is to be inserted when a rain sensor is not connected)
10.6 GND / 0V
With the default values are input:
”Active” if the contact resistance is smaller than 4kΩ
”Inactive” if the contact resistance is bigger than 8kΩ.
For values between 4 and 8kΩ the result will depend on the supply voltage.
Input has pull up approx. 1mA. (min 0.7mA, max 1.4mA)
Example: Wind/rain and rain sensors
WLA 330 and WLA 331 the settings of the sensors are set on the sensor.
J1
Connection for power supply
J3
Connection for battery (power back-up)
J8
USB host. Used for event log creation for e.g. error detection
J9
USB device. Used for remote control and update of firmware
P1
Power supply control
R / P
Reset / Programming (used for firmware updates)
DS 1 /
DS 2
2 DIP switch blocks with 8 DIP switches each
1.1 230V power failure
1.2 Momentary action CLOSE (comfort ventilation)
1.3 Momentary action OPEN (comfort ventilation)
1.4 System fault triggers alarm
1.5 VdS triggering by alarm
1.6 Smoke detector CLOSE (primarily used in Switzerland)
1.7 24V / 48V input active (primarily used in France)
1.8 Actuators with higher run time than 61sec (both closing and opening speed)
2.1 Run time limitation (comfort ventilation)
2.2 Run time limitation (comfort ventilation)
2.3 Run time limitation (comfort ventilation)
2.4 Re-activation of run time limitation (OPEN)
2.5 20A on output X1
2.6 Simple cable monitoring
2.7 No grace timer
2.8 Disable low stand-by power
See section 11 for further detail
LED
Shows the status of the panel
Red = alarm
Yellow = fault
Green fast flickering = all OK (CPU working), Green constant = CPU communication stopped (possible reset or
contact WindowMaster)
↓ ↑
Close / open all windows. When pressed together right after power has been connected the panel configures /
registers connected components.
Input circuit (simplified)

Table of Contents

Related product manuals