EasyManua.ls Logo

Window Master CompactSmoke WSC 320 - Page 24

Default Icon
27 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24
Example of an error message
”7 blinks 1sec. pause 2 blinks 1 sec. pause 1 blinks”.
1. There is an error on a local input
2. The error is on input X10.5, to which a rain sensor might be connected
3. The error is due to no connection to the sensor.
If there are more errors on the panel simultaneously, they are shown with priority, i.e. the error message for the most critical error is
shown first and repeated until rectified. Then the error message number 2 is shown and repeated as well until the error is rectified
etc.
Below table, list the most common errors.
Error message
1. Blink sequence
2. Blink sequence
3. Blink sequence
Number
of blink
Error on
Number
of blink
Error on or error type
Number
of blink
Error type
1
System
1
Internal error (Watchdog
reset)
2
Internal error (Program
CRC)
3
Smoke
zone
1
Max temp. in the panel has
been exceeded re-
configure and check the
panel, see section 13 for
re-configuration of the
smoke panel
5
Actuator
1
X1 (actuator output)
1
Actuator configuration check the actuators,
check the configuration, when using ±24V
standard actuators check the termination
2
Expected number of actuators, the found and
expected number of MotorLink
®
actuators does
not match check actuator connections
4
Internal error
2
X2 (actuator output)
1
Actuator configuration check the actuators,
check the configuration, when using ±24V
standard actuators check the termination
2
Expected number of actuators, the found and
expected number of MotorLink
®
actuators does
not match check actuator connections
4
Internal error
6
WSK-
Link™
1
Bus
1
Closed ring the standard version does not
allow break glass units connected in a closed
ring, check connection of break glass units and
disconnect the ring and re-configure
2
Problem on X5 (break glass unit)
communication with the break glass unit
cannot be established
3
Problem on X6 (break glass unit)
communication with the break glass unit
cannot be established
2
WSK
1
Problem (short circuit, cable problem or
termination) with break glass unit #2
connected to a break glass unit check
connection of break glass unit and termination
smoke detector input
2
Slave panel the standard version does not
allow connection of a slave panel. Remove the
slave panel and re-configure
3
Offline break glass unit, one or more break
glass are offline check and re-configure
4
Break glass unit sensor (smoke detector
connected to break glass unit) check
connection between break glass unit, sensor
and end-module (termination)
5
The break glass unit version is too old break
glass units must be renewed

Table of Contents

Related product manuals