5.3.3 Flue pipe length
When the flue pipe is long and runs through a cold space,
condensate can form. If the straight length of the flue pipe
is longer than 4 meters, the condensate will not evaporate
and accumulate in the heater. In this case. To prevent this:
Insulate the flue pipes.
or
Place a condensate trap (figure 16).
T-piece (6) Condensate
trap (7)
Condensate
drain
Ø80 art. IA8223 IA8225 IA8286
Ø100 art. IA8176 IA8188 IA8288
6
7
Figure 16 - A T-piece (6) and condensate trap (7)
Figure 17 - Condensate drain
5.4 Installation of the flue terminal
There are flue terminals available for installation through a
roof or through a wall.
NOTICE The flue terminal must be installed according to
local and national regulations.
NOTICE Do not combine components or materials from
dierent manufacturers.
5.4.1 Installation - Roof terminal
To install the flue terminal in the roof, do the following:
5.4.1.1 Preparation
1. Check all components for possible damage.
2. Determine the roofing type:
Flat roof flashing Synthetic tile
Universal
pitched roof
flashing.
3. Determine where the flue terminal will be
positioned.
5.4.1.2 Installation
1. Create a hole from the outside of the roof.
CAUTION! Make sure no debris or dust gets into the air
heater.
2. Install the weather collar.
3. Carefully insert the flue terminal from the outside.
CAUTION! Do not rotate the cap.
4. Put the flue terminal into a vertical position. Use a
level.
5. OPTIONAL - If desired, fit cover plates. These are
supplied separately.
6. Place the supplied wall clamp around the flue
terminal and fit it to the roof construction. Do not
tighten the clamp yet.
7. Connect the gasket and the twin-tube connection.
Make sure that the gasket is not damaged.