EasyManua.ls Logo

Wolf CGB-2 - Burner Component Inspection

Wolf CGB-2
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16 3064812_201804
Removingthecombustionchambercover
Open the retaining tabs for the combustion chamber
cover at the front and back.
Lift off the gas fan unit with the combustion chamber
cover.
●Visualburnerinspection
In principle, the burner is maintenance-free.
Carry out a visual check of the burner for damage or
deposits.
Replace if damaged, clean in case of deposits (deter-
gent, damp cloth).
After cleaning or replacing the burner, carry out a 100 %
calibration.
- See description HG43 in chapter
“Parameter description”
Replace the burner gasket after replacing or cleaning
the burner.
●Visualinspectionoftheburnergasket
Clean the supporting surface on the combustion cham-
ber cover and the burner ange. Replace the burner
gasket without lubricating it!
●Graphiteseal
Clean the supporting surfaces. Install or replace graphite
seal.
●Visualinspectionofrefractorybrick
Inspect and if required replace refractory brick.
11.Checkingtheburner

Related product manuals