Manual 02879 723PLUS/Analog Load Sharing
Woodward 89
5. TORSNL LEVEL @CLEAR can be adjusted to the reading recorded above
for the TORSIONAL LEVEL after the limit was reduced.
NOTE
The Torsional Limit Function may not be required if the Torsional Filter
function can reduce oscillations sufficiently. This situation is desirable
because the load is not affected while operating at the torsion point.
Conclusion of Setup Procedures
This completes the adjustment chapter. Save the set points by pressing the
“SAVE” key on the Hand Held Programmer or save settings using Control View
or Watch Window (Refer to “help” if you need help). Run through all the set
points and record them in Appendix D for future reference. Settings can also be
saved to a file using Control View or Watch Window for later download. This can
be very useful if a replacement control is necessary or for start-up of another
similar unit. Power down the control for about 10 seconds. Restore power and
verify that all set points are as recorded.
CAUTION—SAVE SET POINTS
To prevent possible damage to the engine resulting from improper control
settings, make sure you save the set points before removing power from the
control. Failure to save the set points before removing power from the
control causes them to revert to the previously saved settings.
Disconnect the Hand Held Programmer from the control (if applicable). Control
View or Watch Window may remain connected or removed from the control at
the end user’s discretion. Close the cover over J1 and re-tighten the retaining
screw if connection is removed.