Pre-Installation
13
Greenstar 4000 – 6 720 891 161 (2020/09)
Primary system considerations - Combi & System appliances
Sealed system
The CH sealed system must be filled using a WRAS approved filling
loop or comply with examples in section 4.1.4 "System fill".
Where the system volume is more than 100 litres or exceeds 2.5 bar
at maximum heating temperature an additional expansion vessel [2]
must be fitted as close as possible to the appliance in the central
heating return.
Pressurise the extra expansion vessel [2] to the same value as the
built-in expansion vessel [1] (default pre-charge pressure is 0.75
bar).
Fig. 4 Additional expansion vessel
[1] Appliance expansion vessel
[2] Additional expansion vessel
[3] Pressure relief discharge
[4] Heating return
[5] Heating flow
Checking the size of the expansion vessel
To determine whether an additional expansion vessel is required: Follow
the steps below:
Calculate the total system volume (litres).
Plot a line vertically on the chart ( Fig. 5).
Determine the central heating maximum operating flow temperature.
Plot a line horizontally on the chart ( Fig. 5).
Determine the pre-charge in the expansion vessel based on static
head, 1 metre = 0.1 bar.
Static head should be measured between the expansion vessel
and the highest point on the system (top of the highest radiator).
Select a curve from the key below (1-5).
System pressure should be set at 0.1 - 0.25 bar higher than the
vessel pre-charge.
It must be at least to the minimum on appliances with an analogue
gauge.
Minimum pressure settings may need to be adjusted to suit on,
appliances with a digital gauge, in the applicable menu function.
Intelligent filling settings may need to be adjusted to suit on,
appliances with the automatic filling accessory, in the applicable
menu function.
If the dissected lines are in area A then no additional expansion is
required.
If the dissected line is in are B then an additional expansion vessel must
be installed ( Fig. 4).
Fig. 5 Curves for the expansion vessel
1 Pre-charge pressure 0.5 bar (minimum)
2 Pre-charge pressure 0.75 bar
3 Pre-charge pressure 1.0 bar
4 Pre-charge pressure 1.2 bar
5 Pre-charge pressure 1.3 bar
A Operational capacity of the expansion vessel (left of the relevant
curve)
B Additional expansion vessel required (right of the relevant curve)
T Maximum operating temperature [ °C]
V Total System Volume [l]
The default pre-charge pressure for the expansion vessel is 0.75 bar
4.1.3 System layouts examples
Sealed primary system - Single central heating circuit:
Typical primary system example
Fig. 6 Single central heating circuit example
[1] Appliance
0010021117-001
3
4
5
2
1
0010036810-001
30
40
50
60
70
80
90
0 100 200 300 400 500 600 700
A
B
3
5
4
2
1
T[°C]
V[l]
1
0010021227-002

Table of Contents

Other manuals for Worcester GR4700iW C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Worcester GR4700iW C and is the answer not in the manual?

Worcester GR4700iW C Specifications

General IconGeneral
BrandWorcester
ModelGR4700iW C
CategoryBoiler
LanguageEnglish

Related product manuals