54 Freedom X Owner’s Guide
Operating During Transition Between Grid Mode and Battery Mode
Operating Limits
Power Output
The Freedom X can deliver up to 1000 watts (Freedom X 1000) and
2000 watts (Freedom X 2000) of continuous utility grade sine wave
AC power
. The wattage rating applies to resistive loads such as
incandescent lights.
Input Voltage
The allowable Freedom X input battery voltage ranges are shown in
the following table:
Operating
Condition
Battery
Vo
ltage Comment
Full Operating
Range
LBCO – 18.0
volts
Assuming the battery is full, the inverter will
operate until battery voltage goes past below
LBCO
a
a. To set LBCO, see “Adjusting Feature Settings in Configuration Mode” on page 45.
and LBCO Shutdown delay timer
b
b. To set LBCO Shutdown Delay Timer, see “Adjusting Feature Settings in Configuration
Mode” on page 45.
.
Low Voltage
Ala
rm
< LBCO+0.5
volts
A low battery warning shows error code on
the LCD screen.
Low Voltage
Sh
utdown
< LBCO The buzzer sounds a single one-second low
battery alarm beep and the LCD screen shows
error code . After LBCO Shutdown delay
timer runs out, the unit shuts down inverter
output. The buzzer stops beeping and the LCD
screen shows error code .
Instant Low
V
oltage
Shutdown
< 10.2 volts After two seconds below the
limit, the unit shuts
down inverter output completely. LCD screen
turns off completely.
High Voltage
Shutd
own
18.0 volts The display shows error code alternating
with the battery voltage.
The red status LED turns on.
NOTE: Although the Freedom X incorporates
over-voltage protection, it can still be damaged if
input voltage exceeds 18.0 volts.
Operating
Condition
Battery
Voltage Comment
Freedom X Series INV Owners Guide.book Page 54 Tuesday, June 27, 2017 4:10 PM