Table 4 Required AC wire size vs. required breaker rating
Required Breaker Size (amps) Required Wire Size
Freedom Xi 1000
120
VAC
30 A maximum 10 AWG
Freedom Xi 2000
120
VAC
30 A maximum 10 AWG
16 Freedom Xi Installation Guide
Basic Installation Procedures
The AC input terminal is located on the front panel and is labeled
properly as AC IN or AC INPUT. Depending on the model, you can
have three types of wire terminals.
The Standard models come with
WAGO-type terminals where
individual wires can be attached securely.
When making the AC input and AC output connections, observe the
correct color code for the appropriat
e AC wire, as described in
Table 5.
Table 5 Color codes for typical AC wiring
Color AC Wire
Black Line
White Neutral
Green or bare copper Ground (Earth)
NOTICE
EQUIPMENT DAMAGE
Make sure the wires are connected properly. The AC wiring terminal
blocks are split into input and output sections.
Failure to follow these instructions can damage the unit and/or equipment.
Freedom XI Install Guide.book Page 16 Friday, September 18, 2015 2:48 PM