975-0753-01-01 17
Basic Installation Procedures
This guide for use by qualified personnel only.
Wiring Knockouts When installing wires to AC terminals,
always remove the appropriate wiring knockouts (there are two on
each side, two on each AC compartment cover plate) and install the
proper strain-relief bushings.
AC Input Connections for Standard Models
1. Ensure AC and DC power sources are turned off.
2. Install the required circuit breaker in the AC distribution panel
supplying AC power to the unit.
3. Remove the AC compa
rtment cover plate.
4. Strip a single strand (e.g. Romex
®
)
1
AC input wire, as appropriate.
5. Locate the Line, Ground and Neutral terminals o
n the AC input
terminal labeled as L, G, and N respectively.
6. Using a 3.5mm slot long neck screwdriver, open the WAGO cage
clamp by inserting the tool in the clamp slot and gently pulling the
screwdriver handle forward, for Ground terminal.
7. Insert Ground AC wire into Ground terminal slot on the unit.
8. Repeat steps 6 and 7 for Line an
d Neutral connections.
9. Replace the AC compartment cover plate onto the unit.
10. Connect the other end of the wires to the circuit breaker in the AC
distribution panel supplying AC power to the unit.
NOTICE
REVERSE POLARITY DAMAGE
Make sure the wires are connected properly. Improper connections
(connecting a line conductor to a neutral conductor, for example) will
cause the Freedom Xi to malfunction and may permanently damage the
inverter. Damage caused by a reverse polarity connection is not covered
by your warranty.
Failure to follow these instructions can damage the unit and/or equipment.
1.Romex is a brand name owned by Southwire and used here as an example but not as
an endorsement of a particular brand.
Freedom XI Install Guide.book Page 17 Friday, September 18, 2015 2:48 PM