Section 2. Installation
AC Input Power Connection
Release 1.2 23
AC Input Power Connection
The AC input connector is a standard IEC 320 male connector located on the power
supply’s rear panel.
Table 2.2 Operational AC Input Voltage Ranges and Frequency
AC Input
Cord
The AC input cord that we provide is appropriate to the destination country. If you
require a special cord, call us.
WARNING
There is a potential shock hazard if the power supply chassis and cover are not
connected to an electrical ground via the safety ground in the AC input connector.
Ensure that the power supply is connected to a grounded AC outlet with the
recommended AC input connector configured for the available line voltage as
described in this section.
!
CAUTION
When the power switch is turned on, the output voltage or current previously set is
applied to loads.
AC Voltage Range Frequency
104–127 Vac 1
φ (standard) 47–63 Hz
200–250 Vac 1
φ (AC200 option) 47–63 Hz
WARNING
The AC input cord is the disconnect device for the power supply. The plug must
be readily identifiable by and accessible to the operator. The input cord must be
no longer than 9.85 feet (3 m).