EasyManua.ls Logo

Xantrex Trace DR Series - AC Output Wiring to Sub-panel

Xantrex Trace DR Series
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
28
2.0 INSTALLATION
©2000 Xantrex Technology Inc.
NOTE: The two neutral connections (input and output) are common to one another and may be used
in any combination.
AC Wiring (continued)
AC Output Wiring to the Sub-panel
WARNING: ENSURE THE SUB-PANEL DOES NOT HAVE A NEUTRAL TO GROUND BOND. IF IT
DOES, REMOVE IT. ALL AC NEUTRAL-GROUND BONDING IS DONE AT THE MAIN UTILITY
BREAKER BOX (SERVICE ENTRANCE).
Connect the GROUND wire to the inverters AC GROUND chassis terminal. Connect the
other end of this wire to the GROUND bus in the sub-panel.
Connect the NEUTRAL (white) wire to the inverters NEUTRAL OUTPUT terminal. Connect
the other end of this wire to the NEUTRAL bus in the sub-panel.
Connect the HOT (black) wire to the inverters terminal labeled AC HOT OUTPUT. Connect
the other end of this wire to the sub-panels input circuit breaker.
Torque all inverter terminal block connections to 16 inch-pounds. Refer to the sub-panel
manufacturers specifications for wire torques.
Figure 24
AC Output Wiring
AC CHASSIS
GROUND
NEUTRAL
OUT
HOT
OUT

Related product manuals