2.0 INSTALLATION
©2000 Xantrex Technology Inc.
NOTE: The two neutral connections (input and output) are common to one another and may be used
in any combination.
AC Wiring (continued)
AC Output Wiring to the Sub-panel
WARNING: ENSURE THE SUB-PANEL DOES NOT HAVE A NEUTRAL TO GROUND BOND. IF IT
DOES, REMOVE IT. ALL AC NEUTRAL-GROUND BONDING IS DONE AT THE MAIN UTILITY
BREAKER BOX (SERVICE ENTRANCE).
Connect the GROUND wire to the inverters AC GROUND chassis terminal. Connect the
other end of this wire to the GROUND bus in the sub-panel.
Connect the NEUTRAL (white) wire to the inverters NEUTRAL OUTPUT terminal. Connect
the other end of this wire to the NEUTRAL bus in the sub-panel.
Connect the HOT (black) wire to the inverters terminal labeled AC HOT OUTPUT. Connect
the other end of this wire to the sub-panels input circuit breaker.
Torque all inverter terminal block connections to 16 inch-pounds. Refer to the sub-panel
manufacturers specifications for wire torques.
Figure 24
AC Output Wiring
AC CHASSIS
GROUND
NEUTRAL
OUT
HOT