32
Suitable Model: MP360-LMP760-T
Suitable Model: MP330-S.
4. 8-pin round male port of FC/XC series PLC (Port1Port2)
3-2 FX/Q series of Mitsubishi
1. Software settings
Parameters
Recommended Settings
Download Port
9-Pin communication port
PLC Port
Programming Port/FX-422BD
Communication Type
RS422
Communication Distance
70m
Data Bit
7
Stop Bit
1
Verification Mode
Even
Baud Rate
9600
Modbus Number
0
2. Address