V5 series inverter 
56 
To obtain the best energy-saving effect, user can select V/F curve 1, 2, 3 for fan, pump load. 
 
Fig.4-7  V/F curve 
 
Fig. 4-8    User-defined V/F curve 
When P0.22 = 4, you can define V/F curve via modifying (V1, F1), (V2, F2), (V3, F3) to satisfy the special load require-
ment, as shown in Fig.4-8. Torque boost is suitable for user-defined V/F curve. In Fig.4-8.   
Vb  =Torque boost(P0.09)×  V1 
4-2-2. Parameters of frequency setting (Group P1) 
P1.00  Time constant of analog filter  Range: 0.01~30.00s  0.20s 
The inverters filter time for sample value when set the frequency by analog channel. If the wiring is too long or noise is too 
serious, increase this parameter to improve the frequency stability. The longer the filter time, the stronger the noise immun-
ity ability. However, the reponse will be slower.   
P1.01  The gain of VI channel  Range: 0.01~9.99  1.00 
P1.02  Min setting of VI  Range: 0.00~P1.04  0.00V 
P1.03  Frequencyof VI min setting  Range: 0.00~upper limit of frequency  0.00Hz 
P1.04  Max setting of VI  Range: P1.04~10.00V  10.00V 
P1.05  Frequency of VI max setting    Range: 0.00~upper limit of frequency  50.00Hz 
P1.06  Gain of CI channel  Range: 0.01~ 9.99  1.00 
P1.07  Min setting of CI  Range: 0.00~ P1.09  0.00V 
P1.08  Frequency of CI min setting  Range: 0.00~upper limit of frequency  0.00Hz 
P1.09  Max setting of CI  Range: P1.07 ~10.00V  10.00V 
P1.10  Frequency of CI max setting    Range: 0.00~upper limit of frequency  50.00Hz 
P1.11  Max input pulse frequency of PULSE  Range: 0.1~20.0K  10.0K 
P1.12  Min setting of PULSE  Range: 0.0~P1.14  0.1K