V5 series inverter 
16 
 
2-2. Wiring   
 
 
 
  Wiring after power off for at least 10 minutes, otherwise, an electronic short may occur. 
  Do not connect AC power to output terminals U, V and W. 
  Both the inverter and the motor should be safety grounded as there is leakage current inside the inverter.The diameter 
of grounding copper cable must be more than 3.5mm², grounding resistor must be less than 10ohm. 
  Withstand voltage test of the inverter has been done in the factory, users would better not do it again. 
  Do not install electromagnetic contactor, absorption capacitor or other resistance-capacitance absorption devices, as 
shown in Fig2-3.   
  In  order to  make the input  over-current  protection and  power  off  maintenance  easily, the inverters should connect 
power supply via braker. 
  The connection cable of relay I/O circuit (X1~X6, FWD, REV, OC, DO) should select the twisted-pair or shield cable 
with diameter over 0.75 mm². One terminal of the shield layer should be hung in the air and the other terminal should 
be connected with the inverter’s grounding terminal E, the cable length should be less than 50m. 
 
 
 
 
 
2-3. Wiring of main circuit terminals 
2-3-1. Wiring diagram 
 
  Fig. 2-3 Wiring of main circuit 
Caution 
Danger 
  Before layout operation, make sure the power supply of inverter is cut off, all the LED on the operate panel is black out 
and delay for more than 10 minutes. 
  Wiring work can be performed after the voltage between internal electrolesis capacity “+” and “–” is below DC36V. 
  Wiring work can only be done by trained and professional personnel. 
  Before power on,  please check if the power supply voltage is consistent with the inverter voltage level, otherwise 
device damage, human injuries and deaths may occur.